Fire-Safe Material Requirements for Schools, Child Care Centres, Karaoke Establishments, Places of Public Entertainment and Amusement: A Complete Comparison of False Ceilings, Partitions, Curtains, Carpets and FS251

Mention fire retardant paint and many people think only of restaurants. In fact, for premises in Hong Kong that need a licence or registration, including converted school premises, tutorial schools, child care centres, karaoke establishments, places of public entertainment, and places of amusement such as billiard halls, bowling alleys and skating rinks, the Fire Services Department's (FSD) fire safety requirements contain similar provisions on combustible materials. Different types of premises share common requirements, but each also has its own special rules. This guide compares the requirements across premises types in one table, then explains what is special about each, to help operators, designers and fitting-out contractors prepare everything in one go before opening.

Quick answer: The fire safety requirements for converted school premises, child care centres, karaoke establishments, places of public entertainment and places of amusement generally require combustible materials used for false ceilings, partitions or wall finishes to meet Class 1 or Class 2 surface spread of flame under BS 476 Part 7, or another standard accepted by the Director of Fire Services. Non-compliant materials must be treated by a Class 2 Registered Fire Service Installation Contractor with a fire retardant paint or solution accepted by the Director, and an FS251 submitted to the FSD on completion. Drapes and curtains must be made of fire-resisting materials or treated with fire retardant solution. Each type of premises also has special requirements: for example, school premises expressly cover acoustic and thermal linings, drapes at exits in places of public entertainment must be split in the centre, and karaoke carpets have an exception based on area and pile height.

Contents

  1. Summary of requirements by premises type
  2. Requirements common to all premises
  3. Converted school premises and tutorial schools
  4. Child care centres
  5. Karaoke establishments
  6. Places of public entertainment
  7. Billiard halls, bowling alleys and skating rinks
  8. Clubs, guesthouses and other premises
  9. Key differences between premises
  10. General pre-opening checklist
  11. Frequently asked questions

1. Summary of Requirements by Premises Type

Premises typeUsual licensing or registration authorityCombustible material requirementExamples of special requirements
Converted school premises, tutorial schoolsEducation Bureau (fire safety requirements from the FSD)BS 476 Part 7 Class 1 or Class 2, including acoustic, thermal and decorative liningsTreatment by a Class 2 contractor with an FS251 submitted
Child care centresSocial Welfare Department (fire safety requirements from the FSD)BS 476 Part 7 Class 1 or Class 2Drapes and curtains must be made of fire-resisting materials
Karaoke establishmentsFEHD or the Home Affairs Department's Office of the Licensing Authority (depending on location)BS 476 Part 7 Class 1 or Class 2Special requirements for carpets and upholstered furniture; managers must be trained
Places of public entertainmentFEHD (fire safety requirements from the FSD)BS 476 Part 7 Class 1 or Class 2Drapes at exits must be split in the centre and kept off the floor; theatre stages need a safety curtain
Billiard halls, bowling alleys, skating rinksFEHD (fire safety requirements from the FSD)BS 476 Part 7 Class 1 or Class 2Fire service installations in line with the size of the venue
RestaurantsFEHD (fire safety requirements from the FSD)BS 476 Part 7 Class 1 or Class 2Requirements for windows, food service hatches and seating divisions

The table reflects general situations. Licensing authorities and specific requirements vary with the nature, location and size of the premises, and the detailed requirements are those set out in the written notice issued by the FSD or licensing authority for the individual premises. For detailed restaurant requirements, see Fire Retardant Paint and False Ceiling Requirements for Restaurants.

2. Requirements Common to All Premises

The Combustible Materials Provision

Across the fire safety requirements the FSD issues for different premises, the wording on combustible materials is highly consistent:

This means that whether you are opening a tutorial centre, a child care centre or a karaoke establishment, the basic approach to combustible fitting-out materials is the same. For a detailed explanation of the standard, see BS 476 Part 7 Class 1 vs Class 2.

Drapes and Curtains

Requirements for many types of premises also state that drapes and curtains (where installed) must be made of fire-resisting materials, generally meeting BS 5867 Part 2 Type B, or be treated with a fire retardant solution accepted by the Director of Fire Services. This work must likewise be carried out by a Class 2 registered contractor, who submits an FS251.

Maintenance and Alteration of Fire Service Installations

All fire service installations and equipment in the premises must be retained and kept in efficient working order. All maintenance, alteration and addition works on fire service installations and equipment must be carried out by a Registered Fire Service Installation Contractor, who must issue an FS251 to the owner within 14 days of completing the works and send a copy to the FSD. The contractor responsible for alteration or addition works must also submit a Certificate of Compliance (FSI/314A, FSI/314B or FSI/314C, whichever applies) to the FSD.

Electronic Fire Certificates

The FSD has introduced an electronic system for issuing fire licences and certificates, under which fire certificates are sent by email to the address provided by the applicant. Applicants can also use electronic forms to submit documents or notices of completion of fire safety requirements. As for the FS251, from 1 July 2026 it must be prepared and submitted electronically; see The Fire Retardant Paint Process Explained: 12 Steps to FS251.

3. Converted School Premises and Tutorial Schools

Tutorial schools, interest classes or private schools opened in commercial building or shopping mall units are mostly "converted school premises". The FSD's fire safety requirements for converted school premises state that all combustible materials used for false ceilings, partitions or wall finishes, including all linings used for acoustic, thermal or decorative purposes, must meet BS 476 Part 7 Class 1 or Class 2 or an equivalent international standard, or be treated with a fire retardant paint or solution accepted by the Director.

Special Points for School Premises

A Common Scenario

A tutorial centre divided a commercial building unit into several small classrooms with plywood partitions and added acoustic insulation inside them. At inspection, the FSD asked for fire performance proof for both the plywood and the acoustic insulation. Because the insulation was sealed inside the partitions and could no longer be treated, parts of the partitions had to be opened up to replace the material. The safer approach is to choose acoustic materials with test reports at the design stage and complete fire retardant treatment of the plywood before painting. For whether different materials can be treated, see Which Materials Can Be Fire Retardant Treated?.

4. Child Care Centres

Child care centres are used by young children with limited ability to evacuate, so fire safety requirements are correspondingly strict. The FSD's requirements likewise call for combustible materials in false ceilings, partitions and wall finishes to meet BS 476 Part 7 Class 1 or Class 2, or be treated with a fire retardant paint or solution accepted by the Director, and require drapes and curtains to be made of fire-resisting materials.

Special Points for Child Care Centres

5. Karaoke Establishments

Licensing Arrangements

Karaoke establishments are regulated under the Karaoke Establishments Ordinance (Cap. 573). Those located in licensed restaurants generally apply to the FEHD for a permit; those in licensed hotels, guesthouses or clubs apply to the Home Affairs Department's Office of the Licensing Authority for a permit; and other premises apply to the Office of the Licensing Authority for a licence. Premises with no more than 3 karaoke rooms and a total area not exceeding 30 m² may be exempt.

Combustible Material Requirements

The fire safety requirements in Schedule 1 of the Karaoke Establishments (Licensing) Regulation (Cap. 573A), and the FSD's fire safety requirements for karaoke establishments located in restaurants, likewise state that combustible materials in false ceilings, partitions and wall finishes must meet BS 476 Part 7 Class 1 or Class 2, or be treated with a fire retardant paint or solution accepted by the Director, and that drapes and curtains must be made of fire-resisting materials.

Special Arrangement for Carpets

Karaoke rooms are often carpeted. The FSD's requirements for karaoke establishments located in restaurants set separate requirements for carpets, with one exception: a carpet that does not meet the relevant requirements is still accepted as meeting the fire safety requirements if its pile height does not exceed 10 mm and the carpeted area does not exceed 5% of the area of the protected means of escape (calculated floor by floor). In other words, large or deep-pile carpets need proof that they comply and cannot rely on this exception.

Upholstered Furniture and Acoustic Materials

Other Requirements

On completion, karaoke establishments must submit certificates for fire service installations, electrical installations, gas installations, ventilating systems and fire resisting construction. In addition, at least one manager must complete a fire safety training course recognised by the Director of Fire Services, and an approved fire safety video must be shown to customers before they start singing.

6. Places of Public Entertainment

Places of public entertainment such as cinemas, theatres and performance venues have large concentrations of people, and their fire safety requirements are comprehensive. Besides the combustible materials provision, the FSD's fire safety requirements for places of public entertainment include the following requirements related to fitting-out materials:

Drapes at Exits

Drapes and curtains must be made of fire-resisting materials or treated with fire retardant solution, with the treatment carried out by a Class 2 registered contractor who submits an FS251. Drapes and curtains hung at exits must be split in the centre and kept a specified distance above the floor so as not to obstruct evacuation.

Stage Safety Curtains

Theatre stages must have a safety curtain installed in accordance with the FSD's safety curtain specifications. Stage sets, backdrops and similar installations are also combustible materials, and their fire performance should be confirmed.

Temporary Arrangements at Performance Venues

Temporary sets and decorations used during performances must also meet fire safety requirements. For temporary event arrangements, see Fire Safety Requirements for Exhibition Booths and Mall Events.

7. Billiard Halls, Bowling Alleys and Skating Rinks

Billiard halls, public bowling alleys and public skating rinks are places of amusement. The FSD's fire safety requirements for these venues likewise state that combustible materials in false ceilings, partitions and wall finishes must meet BS 476 Part 7 Class 1 or Class 2, or be treated with a fire retardant paint or solution accepted by the Director.

Special Points for Places of Amusement

8. Clubs, Guesthouses and Other Premises

Clubs, guesthouses, massage establishments, amusement game centres and similar premises may also need licences under the relevant legislation, with fire safety requirements set by the FSD. Specific requirements vary between premises, but the principle of the combustible materials provision is broadly the same. Before opening:

  1. Confirm the type of licence required and the licensing authority
  2. Check the FSD's fire safety requirements for that type of premises
  3. Choose materials according to the requirements at the design stage
  4. When you receive the FSD's written notice, check each material requirement item by item

The FSD website sets out the fire safety requirements, performance pledges, common irregularities and FAQs for each type of licensed and registered premises, searchable by premises type.

9. Key Differences Between Premises

DifferenceMain premises affectedPoints to note
Acoustic and thermal liningsConverted school premises, karaokeRequirements expressly cover acoustic linings; the fire performance of acoustic insulation and sound-absorbing panels must be confirmed
Drapes at exitsPlaces of public entertainmentDrapes at exits must be split in the centre and kept off the floor
CarpetsKaraokeNon-compliant carpets are only accepted when the pile height and area exception conditions are met
Upholstered furnitureKaraoke, restaurantsMust meet the relevant fire safety standards
Stage installationsTheatresA safety curtain is required
Cleaning frequencyChild care centres, schoolsTreated surfaces are more easily affected, so durable materials are preferable
Staff trainingKaraokeManagers must complete a recognised fire safety course

10. General Pre-Opening Checklist

Item to checkConfirmed
The type of licence and licensing authority for the premises have been confirmed□
The FSD's fire safety requirements for this type of premises have been checked□
All false ceilings, partitions, wall finishes and acoustic and thermal linings have been listed□
All drapes, curtains, carpets and upholstered furniture have been listed□
Test reports have been obtained from suppliers and checked□
Non-compliant materials were treated by a Class 2 contractor before painting or enclosing□
The FS251 covers all treated materials□
Special requirements such as exit drapes and carpets have been met (if applicable)□
An FSI/314 certificate has been obtained for alterations to fire service installations (if applicable)□
All documents were compiled before reporting completion□

For fire retardant treatment costs, see How Much Does Fire Retardant Paint Cost in Hong Kong?. For the basics of fire retardant paint, see What Is Fire Retardant Paint?.

11. Frequently Asked Questions

Does a tutorial centre need fire retardant paint?

If the tutorial centre is a converted school premises, combustible materials used for false ceilings, partitions or wall finishes, including acoustic and thermal linings, must meet BS 476 Part 7 Class 1 or Class 2. Materials with test reports can be proven by those reports; non-compliant materials must be treated by a Class 2 registered contractor, who submits an FS251.

Does acoustic insulation in a tutorial centre need to be fire-safe?

Yes. The fire safety requirements for converted school premises expressly cover all linings used for acoustic, thermal or decorative purposes. Once acoustic insulation is sealed inside partitions it is hard to treat, so choose materials with test reports at the design stage.

Are there fire safety requirements for crash padding in child care centres?

Padding used on walls counts as a wall finish, so its fire performance should be confirmed. The specific requirements for a child care centre are those set out in the FSD's written requirements for that premises.

What requirements apply to carpets in karaoke rooms?

Carpets generally must meet the FSD's relevant requirements. For karaoke establishments located in restaurants, a non-compliant carpet is also accepted if its pile height does not exceed 10 mm and its area does not exceed 5% of the area of the protected means of escape on each floor. Large or deep-pile carpets need proof of compliance.

Which department should a karaoke establishment apply to?

Those located in licensed restaurants generally apply to the FEHD for a permit; those in licensed hotels, guesthouses or clubs apply to the Home Affairs Department's Office of the Licensing Authority for a permit; other premises apply to the Office of the Licensing Authority for a licence.

Do small karaoke rooms need a licence?

Premises with no more than 3 karaoke rooms and a total area not exceeding 30 m² may be exempt. However, if the premises is itself another type of licensed premises, it must still meet the fire safety requirements for that type.

What requirements apply to drapes at exits in places of public entertainment?

Drapes must be made of fire-resisting materials or treated with fire retardant solution. Drapes hung at exits must be split in the centre and kept a specified distance above the floor so as not to obstruct evacuation.

What documents are needed when altering fire service installations in the premises?

After completing alteration or addition works, the registered contractor must issue an FS251 within 14 days and send a copy to the FSD, and must also submit a Certificate of Compliance FSI/314A, FSI/314B or FSI/314C, whichever applies, to the FSD.

Is fire retardant paint handled the same way for different types of premises?

The basic approach is the same: materials must meet BS 476 Part 7 Class 1 or Class 2, or be treated by a Class 2 registered contractor who submits an FS251. However, each type of premises has its own special requirements, such as acoustic linings, exit drapes and carpets, which must be handled according to the individual requirements.

Are fire certificates now issued electronically?

The FSD has introduced an electronic system for issuing fire licences and certificates, under which fire certificates are sent by email to the address provided by the applicant.

Fire-Safe Materials Assessment for Licensed Premises

Grand United Eng., Co. is a Registered Fire Service Installation Contractor in Hong Kong. For tutorial schools, child care centres, karaoke establishments, and places of entertainment and amusement, we can assess combustible fitting-out materials, check test reports, arrange fire retardant treatment and the FS251, and handle the installation, alteration and annual inspection of fire service installations in the premises. When you contact us, please provide the premises type, address, floor area, design plans, material schedule and any FSD letter of requirements. You can also browse our Fire Engineering Services, Service Coverage and Project Cases.