Fire Retardant Paint and False Ceiling Requirements for Restaurants: A Complete Guide to Fire-Safe Materials, FS251 and FSD Inspection from Site Selection and Fitting-Out to Licensing
When opening a restaurant, café or snack shop in Hong Kong, designers usually focus most on atmosphere: timber-clad walls, feature false ceilings, fabric curtains and booth partitions. Yet these are exactly the areas where the Fire Services Department (FSD) most often raises requirements when assessing restaurants. Many new outlets are only asked to carry out fire retardant treatment at inspection because they cannot prove their fitting-out materials meet the standard, and some even have to strip out and reinstall, delaying opening. This guide follows the five stages of opening a restaurant to set out the requirements for restaurant fire retardant paint and combustible materials, and explains the FSD's approval process and inspection points.
Quick answer: Combustible materials used for false ceilings, partitions or wall finishes in Hong Kong restaurants must meet Class 1 or Class 2 surface spread of flame under BS 476 Part 7, or another standard accepted by the Director of Fire Services. Curtains and drapes must meet BS 5867 Part 2 Type B. Non-compliant materials must be treated by a Class 2 Registered Fire Service Installation Contractor with a fire retardant paint or solution accepted by the Director, and an FS251 submitted to the FSD on completion. At inspection, the quantity and type of treated materials on site must match the FS251.
Contents
- The restaurant fire safety approval process
- Fitting-out materials restaurants must address
- Handling fire-safe materials at each stage of opening
- FSD inspection points
- How high-risk restaurants are identified
- Other fire safety rules related to fitting-out
- Four common scenarios
- The most common restaurant mistakes
- Frequently asked questions
1. The Restaurant Fire Safety Approval Process
When applying for a General Restaurant Licence or Light Refreshment Restaurant Licence, applicants do not need to apply to the FSD directly. After receiving an application, the Food and Environmental Hygiene Department (FEHD) refers the case to the FSD, the Buildings Department and other departments, which handle fire safety and building safety matters respectively.
How the FSD Handles an Application
- On receiving the referred application and plans, the FSD carries out an initial site inspection and reviews the plans.
- If the location or plans are not acceptable, it raises an objection in writing with reasons, and the applicant may revise and resubmit the plans.
- If the location and plans are acceptable, it issues a written notice listing the fire safety requirements the applicant must comply with.
- Once all requirements are completed, the applicant reports completion in writing, by phone, email or fax.
- The FSD sends staff to inspect, and notifies the applicant in writing of any items not yet compliant.
- Once all fire safety requirements are confirmed as met, the FSD issues a Fire Services Certificate.
The FSD's Performance Pledges
| Stage | Pledged timeframe |
|---|---|
| Issuing fire safety requirements or an objection letter after receiving the application | Within 17 working days |
| Carrying out a site inspection after completion is reported | Within 7 working days |
| Issuing the Fire Services Certificate after all requirements are confirmed as met | Within 7 working days |
As this shows, what most affects the opening date is usually not the government's processing time, but whether the applicant can complete all requirements in one go. If the inspection finds incomplete documents for fire-safe materials, the work has to be redone, completion reported again and another inspection arranged, and each round pushes the opening date back.
Provisional and Full Licences
To help restaurants open sooner, the FEHD operates a provisional licence system. Once an Authorized Person, a Specialist Contractor (Ventilation Works category), a Registered Fire Service Installation Contractor and other relevant professionals certify that the restaurant meets the basic licensing requirements, the applicant may be granted a provisional licence valid for six months to operate in the meantime. During this period, the applicant must fulfil all outstanding licensing conditions as soon as possible to obtain a full licence. Unless the delay is caused by reasons beyond the applicant's reasonable control, all licensing conditions must be fulfilled within 6 months of the provisional licence expiring, or within 12 months of the letter of requirements for a full licence being issued (if no provisional licence was granted).
In other words, a provisional licence is simply a way to start trading earlier. It does not mean the requirements for fire-safe materials can be skipped. Fire retardant treatment and the FS251 must still be completed before a full licence is granted.
2. Fitting-Out Materials Restaurants Must Address
In the fire safety requirements the FSD presents to restaurant applicants, the "fire retardant paint" item covers four types of material: wall finishes, false ceilings, timber partitions and curtains. The applicable standards for each are set out below:
| Material | Common restaurant examples | Applicable standard | Treatment if non-compliant |
|---|---|---|---|
| Wall finishes | Wood-grain wall panels, timber slat feature walls, upholstered wall panels, wallpaper | BS 476 Part 7 Class 1 or Class 2 | Treatment with an accepted fire retardant paint or solution |
| False ceilings | Timber grille ceilings, feature timber ceilings, acoustic ceiling panels | BS 476 Part 7 Class 1 or Class 2 | Treatment with an accepted fire retardant paint or solution |
| Partitions | Timber booth partitions, private room partitions, screens | BS 476 Part 7 Class 1 or Class 2 | Treatment with an accepted fire retardant paint or solution |
| Curtains and drapes | Window curtains, private room drapes, fabric decorations | BS 5867 Part 2 Type B | Treatment with an accepted fire retardant solution |
Whichever method is used, applying fire retardant paint or solution must be carried out by a Class 2 Registered Fire Service Installation Contractor, who submits an FS251 to the FSD on completion. If a material already has a test report showing it meets the standard, the report can serve as proof and no further treatment is needed. For the difference between the two standards and how to check reports, see BS 476 Part 7 Class 1 vs Class 2.
Materials That Are Easily Overlooked
- Wallpaper and wall stickers: when used over large areas, these also count as wall finishes and their standard should be confirmed.
- Upholstered and acoustic panels: the foam or fibre inner layers may be combustible materials.
- Decorative timber slats and grilles: they may look small in area, but there are many of them and their total surface area is large.
- Cashier counter and bar back walls: these form part of the wall finishes.
- Private room drapes: often treated as "soft furnishings" and missed.
3. Handling Fire-Safe Materials at Each Stage of Opening
The best time to deal with fire-safe materials is at the design and procurement stages; the later you leave it, the higher the cost. The five stages of opening a restaurant, and what to do at each, are set out below.
Stage 1: Site Selection
When choosing a site, first confirm that the premises is suitable for restaurant use. FSD information states that restaurants should not be located in industrial buildings, substandard buildings or structures, places intended for emergency use (such as refuge floors), the fourth basement level or below, places designed for other specific uses (such as car parks), or floors below ground level where liquefied petroleum gas is used. Also consider floor area: restaurants in a basement with a floor area over 126 m², or elsewhere with a floor area over 230 m², must install an automatic sprinkler system, which significantly increases fitting-out costs.
Stage 2: Design and Plans
- List the type, location and area of every combustible material in the material schedule.
- Prioritise materials that already have BS 476 Part 7 Class 1 or Class 2 reports.
- Prioritise curtain fabrics that already meet BS 5867-2 Type B.
- Avoid dividing large areas of seating with combustible materials, so that the premises is not classified as higher fire risk (see below).
- Avoid sealing or obstructing windows originally designed to be openable or breakable.
Stage 3: Procurement
Ask suppliers for test reports and check that the product model, thickness, colour and installation method match the report. If the report does not match the actual material, decide before ordering whether to switch to another material, or allow time and budget for fire retardant treatment. For cost factors, see How Much Does Fire Retardant Paint Cost in Hong Kong?.
Stage 4: Fitting-Out Works
Materials needing fire retardant treatment should be treated after assembly but before painting or surface finishing. The fitting-out contractor should allow for this in the programme and book a Class 2 registered contractor about 2 to 3 weeks in advance. For details of the work, see The Fire Retardant Paint Process Explained: 12 Steps to FS251.
Stage 5: Reporting Completion and Inspection
Before reporting completion, compile all documents for fire-safe materials, including test reports and the FS251, and check that the quantity and type of treated materials on site match the FS251. The FSD's inspection checklist states clearly that the quantity and type of combustible materials treated with fire retardant paint or solution must match the FS251 submitted, and that inspections will not be arranged unless the relevant Fire Safety Office has received all necessary supporting documents.
| Stage | Fire-safe material focus | Responsible party |
|---|---|---|
| Site selection | Confirm location and area; anticipate whether a sprinkler system is needed | Owner, designer |
| Design | List combustible materials in the schedule; choose compliant materials | Designer |
| Procurement | Obtain and check test reports | Fitting-out contractor, owner |
| Fitting-out works | Arrange treatment by a Class 2 contractor before painting | Fitting-out contractor, registered contractor |
| Inspection | Check that the FS251 matches materials on site; compile documents | Owner, registered contractor |
4. FSD Inspection Points
Besides fire retardant paint, the fire safety requirements the FSD presents to restaurant applicants include the following items. Inspectors generally check them one by one:
| Item | Focus |
|---|---|
| Fire retardant paint | Material proof or FS251 for wall finishes, false ceilings, timber partitions and curtains |
| Sealed windows | Sealed windows require additional smoke extraction |
| Kitchen fire resistance | Fire resistance requirements for kitchen walls and doors |
| Kitchen food service hatch | Area must not exceed 0.2 m² |
| Exit signs and directional signs | Location, number and illumination |
| Emergency lighting | Coverage and operation |
| Fuel | Arrangements for gas burners, electric griddles, deep fryers and similar |
| Manual fire alarm | Location and operation |
| Portable fire-fighting equipment | CO2 fire extinguishers, water-type fire extinguishers and fire blankets |
How Fire-Safe Materials Are Checked at Inspection
- The location and quantity of treated materials are checked against the plans and the FS251.
- The type of material on site is checked against the documents.
- Where a test report is used as proof, the product in the report is checked against the material on site.
- Curtains and drapes are checked for corresponding documents.
Common reasons for failure include an FS251 that covers only some materials, partitions added on site that are not on the plans, curtains without documents, and materials repainted after treatment.
5. How High-Risk Restaurants Are Identified
The FSD classifies restaurants by fire risk and sets different fire safety standards for each class. The factor most directly linked to fitting-out materials is how seating is divided. Under the relevant FSD standards, if more than 30 per cent of the seating area is divided into one or more compartments with combustible materials, or windows designed to be openable or breakable are obstructed by decorations, the premises may be classified as higher fire risk and must meet stricter requirements.
For designers, this means booth or private room layouts are not just an aesthetic choice. Dividing large areas of seating with timber or fabric may change the premises' risk classification and add requirements for other fire service installations. Assess the extent of divisions before finalising the design, or use non-combustible materials for partitions.
6. Other Fire Safety Rules Related to Fitting-Out
Windows and Smoke Extraction
Unless a dedicated smoke extraction system is installed, windows in food business premises must not be obstructed by decorations, more than 50 per cent of the openable or breakable window area must not be sealed, and no more than 25 per cent of the upper half of such windows may be sealed. Many restaurants seal windows with decorative panels to create atmosphere, only to find that a smoke extraction system is then required, at a cost far higher than expected.
Kitchens and Food Service Hatches
The Buildings Department's requirements for restaurants state that kitchens should generally be enclosed by walls and floors with a fire resistance rating of not less than 1 hour, with doors rated at not less than half an hour. Food service hatches in kitchen walls with an area not exceeding 0.2 m² must be fitted with a fire shutter rated at not less than half an hour. FSD standards also state that if a food service hatch exceeds 0.2 m², a fire shutter approved by the Director of Fire Services must be installed. Check these limits before designing an open kitchen or large service counter.
Upholstered Furniture
Polyurethane foam upholstered furniture in the premises, such as sofas and padded seats, must comply with BS 7176 (1995) for resistance to ignition of upholstered furniture for non-domestic seating by testing composites (medium hazard premises), or another standard approved by the Director of Fire Services. Ask for the relevant test reports when buying seating.
Ventilation Systems
Restaurants are covered by the relevant ventilation regulation (Cap. 132CE) and need a separate letter of compliance for the ventilating system. Ventilation ducts must be made of non-combustible materials, air filters must use non-combustible materials, and insulation within ducts must also meet FSD requirements. This part is handled by a Specialist Contractor (Ventilation Works category), but like fitting-out materials it concerns "combustible materials" and should be considered during fitting-out.
For an overview of Hong Kong fire safety legislation, see Hong Kong Fire Safety Laws and Regulations. For installing other fire service installations, see our Fire Engineering Services.
7. Four Common Scenarios
Scenario 1: A Japanese-Style Timber Café
Situation: walls and ceiling are clad throughout with solid timber slats, with timber screens dividing the seating.
Key points: there are many slats with a large total surface area, so quotations should be based on actual surface area rather than wall area. For the timber screens, assess whether the divided area exceeds 30 per cent, to avoid affecting the risk classification.
Recommendation: arrange fire retardant treatment before the slats are stained or oiled. If the design calls for a natural timber look, confirm what the fire retardant product will look like after treatment.
Scenario 2: A New Branch of a Restaurant Chain
Situation: the design follows the flagship outlet, with materials from the same supplier.
Key points: even if the flagship already holds a licence, the new branch must still provide proof for the materials on its own site. Supplier reports must match the models purchased this time.
Recommendation: build a standard material library with test reports prepared in advance for every material, so new outlets can reuse them and greatly reduce fire retardant treatment.
Scenario 3: Renovating a Restaurant in Operation
Situation: a licensed restaurant replaces some wall finishes and adds private room partitions.
Key points: material changes during the licence period must also be checked against flammability standards, with test reports or an FS251 kept on file. Otherwise this may be treated as a breach of licensing conditions.
Recommendation: carry out the work outside opening hours and update the document file once the changes are complete.
Scenario 4: Opening First on a Provisional Licence
Situation: the owner wants to start trading as soon as possible and applies for a provisional licence first.
Key points: the provisional licence is valid for six months, and the FS251 for fire-safe materials must still be completed before the full licence is granted.
Recommendation: do not leave fire retardant treatment until after opening. Working while the restaurant is trading is harder and may affect customers.
8. The Most Common Restaurant Mistakes
- Not listing combustible materials at the design stage: omissions are only discovered at inspection.
- Painting timber before treatment: fire retardant products cannot adhere, so materials must be replaced or coatings removed.
- Assuming curtains are not part of the fitting-out: curtains and drapes also need documents.
- An FS251 that does not match the site: partitions are added or materials replaced after treatment without updating the documents.
- Sealing windows with decorations: this triggers the smoke extraction requirement.
- Extensive booth divisions: these can lead to the premises being classified as higher fire risk.
- Fire retardant paint applied by unregistered persons: no valid FS251 can be obtained, so the work must be redone.
Fire-Safe Materials Checklist for Opening
| Item | Confirmed |
|---|---|
| A material list for all false ceilings, partitions, wall finishes and curtains has been compiled | □ |
| Test reports have been obtained from suppliers and checked | □ |
| The extent of seating divisions has been assessed | □ |
| No windows are sealed or obstructed, or a smoke extraction system has been arranged | □ |
| The food service hatch area and fire shutter arrangements have been confirmed | □ |
| BS 7176 reports have been obtained for upholstered seating | □ |
| Materials needing treatment were treated by a Class 2 contractor before painting | □ |
| The quantity and type of materials covered by the FS251 match the site | □ |
| All documents were compiled before reporting completion | □ |
9. Frequently Asked Questions
Does every restaurant need fire retardant paint?
Not necessarily. If the materials used for false ceilings, partitions, wall finishes and curtains already have test reports showing they meet the standard, the reports can serve as proof and no further treatment is needed. Only combustible materials that cannot be shown to comply must be treated with fire retardant paint or solution by a Class 2 registered contractor, with an FS251 submitted.
Do restaurant licence applicants need to apply to the FSD directly?
No. After the applicant submits an application to the FEHD, the FEHD refers the case to the FSD. The FSD then inspects the site, reviews the plans and issues written fire safety requirements.
How long does the FSD take to issue fire safety requirements?
Under the FSD's performance pledges, fire safety requirements or an objection letter are issued within 17 working days of receiving the application. A site inspection is carried out within 7 working days of completion being reported, and the Fire Services Certificate is issued within 7 working days of all requirements being confirmed as met.
Must fire retardant paint be completed during the provisional licence period?
A provisional licence allows a restaurant that meets basic licensing requirements to start trading. The applicant must still fulfil all outstanding licensing conditions, including fire safety requirements, as soon as possible during its validity to obtain a full licence. Completing fire retardant treatment before opening is recommended.
Is it a problem to use timber partitions for restaurant booths?
Timber partitions must meet BS 476 Part 7 Class 1 or Class 2, or be treated with fire retardant. In addition, if more than 30 per cent of the seating area is divided into compartments with combustible materials, the premises may be classified as higher fire risk and must meet stricter requirements.
Can a restaurant seal its windows?
Unless a dedicated smoke extraction system is installed, windows must not be obstructed by decorations, and no more than 50 per cent of the openable or breakable window area, or 25 per cent of the upper half of such windows, may be sealed.
Are there fire safety requirements for restaurant sofas and upholstered seats?
Yes. Polyurethane foam upholstered furniture must comply with BS 7176 (1995) for medium hazard premises, or another standard approved by the Director of Fire Services. Ask for test reports when buying.
If a licensed restaurant is renovated, do fire-safe materials need to be addressed again?
If new combustible materials are used or the fitting-out is altered during the licence period, the flammability standard of the materials must be confirmed and a test report or FS251, whichever applies, submitted. Otherwise this may be treated as a breach of licensing conditions.
Must the materials covered by the FS251 match the site exactly?
Yes. The FSD's inspection checklist states that the quantity and type of combustible materials treated with fire retardant paint or solution in the premises must match the FS251 submitted. If materials are added or replaced after treatment, they should be treated again and the certificate updated.
Restaurant Fire-Safe Materials Assessment
Grand United Eng., Co. is a Registered Fire Service Installation Contractor in Hong Kong. During restaurant design and fitting-out, we can help assess combustible materials, check test reports and arrange fire retardant treatment and the FS251. We also handle fire service installations such as exit signs, emergency lighting and portable fire-fighting equipment, helping you meet all fire safety requirements in one go and reduce repeat inspections. When you contact us, please provide the premises address, floor area, design plans, material schedule and any FSD letter of requirements. You can also read our fire retardant paint basics and browse our Project Cases and Service Coverage.