Grand United Eng., Co.
Frequently Asked Questions
60 most frequently asked by owners, business owners ' law groups, management companies, tenants and regulators on this pageFire EngineeringIssues, coverageRegistered Fire Service Installation ContractorLevel (level)Class 1/ Class 2 / Class 3 fire safety contractorYes, RC1/RC2/RC3 contractor)、FS251 CertificatewithAnnual Fire Safety Inspection、Annual fire safety inspectionwithannual fire safety inspection "、fire extinguisher annual inspectionandFire Extinguisher Servicing、fire protection system design、fire protection system installed、fire protection system change、fire protection system maintenance、fire equipment maintenance, fire safety plans approval and fire safety acceptance inspection process.
All legislative and procedural information is organized in accordance with the fire safety regulations (chap. 95), fire safety (instruction contractor) regulations (chapter 95A), fire safety (setters and equipment) regulations (chap. 95B), safety (business premises) regulations (Chapter 502), safety (buildings) regulations (chap. 572), fire safety (industrial buildings) regulations (Chap. 636). Practical requirements for individual property industries vary according to use, size, year of construction and conditions on the ground, and it is recommended that specific case-by-case consultations be conductedfire safety adviserorDirect liaison with us。
I. registered fire service installation contractor and level (RC1/RC2/RC3)
What is the registered fire service installation contractor?
Registered Fire Service Installation ContractorIt is registered with the Fire Services Department by a company or trade number under Chapter 95A of Hong Kong legislation, fire safety (container) Regulations, class 1, level 2 and level 3. The installation, maintenance, repair and inspection of fire service installations or equipment in the premises shall be performed by a registered fire service installation contractor under Chapter 95B.
In other words, anyfire service installationsNeither (whether new, modified, repaired or annual inspection) is the work that may be performed by a general whistle-blower, while the registration level determines which type of system that the contractor can legally process. Extended reading:Hong Kong fire safety regulations。
Class 1; Class 2; Class 3 fire safety contractor (RC1, RC2, RC3)?
The three levels are divided according to the nature of the mechanism(s) that can be handled:
| Level | Possible work | Common counterpart system |
| Level 1 ( Class 1 fire safety contractor /RC1 contractor ) | Devices, maintenance, repairs and inspection of electrical or other instruments to detect smoke or fire, and fire service installations or equipment (except hand-held equipment) that would alarm or otherwise issue warnings | fire alarm system, mobile fire alarm ⁇ , smoke detector, heat detector, fire alarm bell |
| Level 2 ( Class 2 fire safety contractor /RC2 contractor ) | Devices, maintenance, repair and inspection of fire service installations or equipment (except hand-held equipment), including plumbing and fittings designed or modified for the transmission of water or other fire extinguishers, or other types of electrical devices specified in step 1 | automatic sprinkler system, fire safety tumours and fire hose reel, fire pump, ballast, gaseous fire suppression system, water pumping and water pump systems, smoke-free systems |
| Level 3 ( Class 3 fire safety contractor /RC3 contractor ) | Maintenance, repair and inspection of handheld devices | Fire extinguisher, fire extinguisher, fire blanket |
Part of the system would involve both step 1 and level 2 in the reference classification for Fire Services Department, and it would therefore be prudent to determine which class 1 had been sought to reconcile the list of devices with the contractor.
How can a fire engineering company be checked whether it is registered with the contractor?
Three steps:
- Request for Fire Services Departmentregistered fire service installation contractor registration certificate and registration number。
- Reconciliation of registrationLevelAre your systems covered (e.g. tier 3 contractor with only hand-held fire extinguisher cannot deal with sprinkler or alarm system).
- ReconciliationEffective period of registrationand whether the name of the company is consistent with the name on " , contract and certificate.
The list of registered fire service installation contractor, published by Fire Services Department, can also be checked.
What is the risk of finding a non-registered contractor for fire engineering?
Under Chapter 95B, the installation, maintenance, repair and inspection of fire service installations and equipment shall be carried out by a registered fire service installation contractor. Construction of non-registered persons, with the following substantive consequences:
- No effective access FS251 Certificate of Fire Service Installations and EquipmentAnnual inspection records are empty.
- The licence is blocked (fire safety certificates are often one of the prerequisites for licensing).
- The post-insurance claim may be challenged for failure to meet the statutory maintenance responsibilities.
- Owners or occupants may be prosecuted for failure to comply with statutory requirements.
- Repatriation costs are high: non-compliant devices often need to be re-engineered.
Does a site require multiple levels of contractor at the same time?
Depending on the type of device. A restaurant usually has a tier 1 ( fire alarm bell, detector), level 2 ( sprinkler, copper) and step 3 (fire extinguisher, fire blanket). The separation of three companies is technically feasible, but the common problem is that responsibility for defects is intertwined, certificates are dispersed and inspections take different stages.
If the same contractor is registered at three levels, it will be possible to obtain a uniform inventory, uniform testing, uniform issuance and presentation of certificates. Company I, II, Class 3fire service installations。
What are the separates for the company ' s chicken fire safety advisers?
registered fire service installation contractor is statutory construction and accreditation;fire safety adviserIn general, the role of providing professional advice such as design, legislation compliance, risk assessment and solicitation documents is referred to. The two could be the same company: the advantage of a contractor-designated consultant was that the design phase had considered the feasibility of construction and acceptance inspection, reducing the number of copper design lots and in situ failures.
II. FS251 Certificate of Fire Service Installations and Equipment
What is the certificate?
FS251 Formal nameCertificate of Fire Service Installations and Equipment。 The registered fire service installation contractor, upon completion of the installation, maintenance, repair or inspection of the fire service installations or equipment, must issue such a certificate to the person entrusted with the work and send a copy to the Fire Services Department as required by chapter 95B.
Its role is to prove that the fire service installations in the Service have been checked/processed by qualified contractors and are in an effective operational condition. As a result, owners, legal missions, management companies, tenants and licence departments will use FS251 as compliance vouchers.
How long have the certificate been valid?
FS251 is itself a certificate recording the completion of a work, not a one-year laissez-passer. However, since legislation requires at least one inspection per 12 months, substantive annual inspection FS251 is generally considered to be valid for a year and the next examination must be completed within 12 months to avoid a record vacuum.
It is recommended that the annual inspection date be recorded in conjunction with the lease, licence renewal dates, with an early one to two months ' arrangement.
FS251 by whom?
Issued by a registered fire service installation contractor for implementationPersons entrusted with the work(Processor, owner-institution, management company or tenant), contractor after completion of work 14 daysIssuance of the certificate and delivery of a copy to Fire Services Department. The client shall maintain copies of his or her own copy for presentation at the time of the licence application, renewal, buying and inspection.
Could FS251 be delivered online?
It is possible, and at present it is accepted only in electronic form. Fire Services Department ⁇ Certificate of Fire Service Installations and Equipment (FS251) Online Transmission System operated as from 1 April 2019, through which a registered contractor may prepare and submit FS251, access FS251 records and may use the loaded Excel statement function for one time to upload multiple certificates.
FS251 When is the process of full implementation?
Fire Services Department 2026 1 JulyFully implemented FS251 electronic presentation of certificates. Processes are: contractor ' s input into the system of building addresses, fire service installations categories, inspection results, damage and repairs to be submitted after the completion of electronic signatures of a smart or Hong Kong e-mail certificate, which automatically generates information with a copyTwo-dimensional anti-foundation codeElectronic certificates.
Impact on owners and management: records are uploaded, overdue or less readily identifiable; The certificate can be reconciled with authenticity by a two-dimensional code; The contractor should be selected to confirm that it is in a position to complete the preparation, signature and submission of the new system.
What is the delay in FS251?
According to Fire Services Department, the contractor is required to complete a certificate within the system for delivery to the client and to submit the certificate through the system within the statutory 14-day period; Failure by the contractor to comply with the relevant statutory requirements may be prosecuted for violating the relevant legislation.
As a commissioner, it was suggested that the contractor be offered an electronic copy of the submitted certificate as a archiving certificate from its own party upon completion of the work.
How can the FS251 received be reconciled to be effective?
Checks can be made from four sources: the name of the contractor on the certificate and the registration number, whether the registered level covers the listed devices, whether the date of inspection is different from the date of issuance of the certificate to a reasonable extent (issued within the statutory 14 days) and whether the two-dimensional code on electronic certificates is scanned.
FS251 and FSI/314A, FSI/314B respectively?
The two categories of documentation are different:
- FS251 Certificate of Fire Service Installations and Equipment )
- Accredited by a registered fire service installation contractor after completion of the installation, maintenance, repair or inspection, attesting to the condition of the installation, which is often used for annual inspection and licence.
- FSI/314A, FSI/314B (Compliance/conformity of security certificates)
- According to Fire Services Department, food premises licence applicants are required to obtain a security certificate (FSI/314A or FSI/314B) and/or FS251 issued by registered fire service installation contractor; FSI/314A or FSI/314B (where applicable) shall also be required to carry out retrofitting and assembly works.
Simple note: FS251StatusFSI/314 SeriesCompliance。
III. Annual fire safety inspection: frequency, scope and responsibility
How long did the annual fire safety inspection take place?
All fire service installations and equipment are subject to article 8 (1) of the fire safety (setters and equipment) Regulations, Chapter 95B.Keeping in an effective operational stateand12 monthsOne registered fire service installation contractor inspectionAt least once。 This statutory inspection is alleged by the industryAnnual Fire Safety Inspectionorannual inspection of fire service equipment。
Annual fire safety inspection by side?
Legal responsibilityOwner of fire service installations and equipment。 The substantive division of labour is generally as follows:
| Background | Often by whom |
| Large public utility component (building ladders, corridors, kitchens, utility poles and alarm systems) | Business Corps or Management Corporation |
| Self-use or lessor unit internal device | Owners or tenants, by tenancy clause |
| Additional or modified devices after fitting | The party entrusted with the refurbishment shall be constructed and certified by a registered contractor. |
| Holdings (food premises, houses, schools, etc.) | licence holder |
It is recommended that annual inspection, remedial work and the responsibility to maintain certificates be clearly spelled out in leases or management contracts, which avoid interfering with each other.
What is the annual fire safety inspection?
Depending on physical devices at the site, common ranges include:
- Shanded fire extinguisher and fire blanket: pressure, sealing lead, pharmacies, location and marking.
- fire alarm system: mainframe, round-trip, back-up power supply, hand-held alerts, detector brake tests.
- fire alarm bell : noise and coverage, sub-district sounds.
- emergency lighting and exit sign : electric power testing, photography, direction and visualization.
- fire hose reel and fire safety tumours: water pressure, tubes, spraying, valves, chromosomes and decals.
- automatic sprinkler system : sprinkler head, status and copper, control tumours, flow alarm devices.
- fire pump and pressure: flash, pressure, heterogeneity, control and power sources.
- gaseous fire suppression system: steel bottle weight/pressure, pipes and sprays, connections and alerts.
- door, fire-proofing and ventilation systems: self-contained, connected, relayed, wind and wind.
For details seefire protection system maintenance and annual inspection。
How long does the annual inspection take? Would it affect business?
Small shops, if only fire extinguisher and a small number of alarm devices, are usually completed within hours; Large and medium-sized sites involving sprinkler, kitchens and gas systems may need to take one to several days and be subdistricted.
In order to avoid clock tests affecting customers and neighbours, restaurant, business yards, schools, etc. are often scheduled for non-commercial or night work. A short separation system is required during the testing period, which must be re-located and recorded immediately upon completion.
Is there a need to stop water during the annual inspection?
Most inspections are not required. sprinkler and copper tests may require short closure or operation of specific control pumps, cartridge testing will initiate fire pump, and alarm test will trigger a short shackling of the police clock. The Service, the tenant and the adjacent units should be informed prior to the incident and confirmed the test period.
What are the consequences of not having an annual inspection?
The immediate consequences include the possibility of prosecution for failure to fulfil legal responsibilities under Chapter 95B; (a) The failure of the system at the time of fire to endanger life and property; (a) The application or renewal is blocked; Insurance claims were challenged.
In addition, Fire Services Department has made FS251 information electronically and integrated into the internal system, providing real-time access to inspection and damage of fire service installations in the entire port building and strengthening controls over contractors, so that records gaps are more easily detected than previously.
Are additional annual inspections needed after the completion of the new refurbishment?
The additional or modified portion will be certified upon completion of the renovation work, but the mandatory 12-month inspection cycle continues to apply to all installations throughout the service. The practice is to start with the most recent full inspection date, arrange for the next annual inspection and avoid a long-outstanding record of some devices.
Can units remain vacant for long periods of time, and should they continue to perform annual inspections?
To do so. (a) The obligation to target the owner of the device does not be exempted from unit empty; In addition, emergency lighting batteries are more frequent during airtimes, crash, fire extinguisher leakage. A complete annual inspection prior to the transfer or sale would normally reduce the controversy.
IV. Annual fire safety inspection
Annual fire safety inspection finitely? How can money be calculated?
Hong Kong not uniformAnnual fire safety inspectionTable.Annual fire safety inspection feesThe main depend is on:
| Factors | An explanation |
| Type and quantity of devices | Fire extinguisher, detectors and police clocks, emergency lighting and exit sign number, sprinkler head number, chicken and kiln group |
| Concerning contractor level | The workload gap between fire extinguisher (level 3) and the simultaneous involvement of alarms (grade 1) and sprinkler band (2nd level) |
| Area and floor | Multiple layers of property, industrial building, large business sites need more manpower and time |
| Construction hours | Higher construction costs at night or non-commercial time |
| Whether remedial work is included | Inspection fees generally do not include replacement of spare parts and pharmaceuticals |
| Recorded integrity | Additional time counts are required in the first year if there is no list of devices or old certificates |
The most practical approach: provision of flash maps, lists of devices or the last FS251, with site survey arranged and access to individual itemsannual fire safety inspection "。Immediate request "。
Does the cost include replacement of spare parts?
Generally not included. Annual inspection fees usually cover inspections, functional tests, cleaning colonels, records and issuance and transmission to FS251. If requiredFire Extinguisher ServicingReplace sprinkler head , detector, emergency lighting batteries, exit sign or repair of aluminiumannual fire safety inspection remedial workIt will be added. "
It is recommended that the request for a " caveat and projected remedial work " be specified by the other party, and that the remedial work be confirmed beforehand.
Why is the annual inspection of different companies " a significant gap?
Reasons are common: the scope of inspections varies (some do fire extinguisher, not test alarm or sprinkler), does not include a certificate delivery, does not cover night work, does not contain a review, or is not counted in expendable material. The comparison should be based on a cross-reference between the number and the project, rather than on the total price.
What is the range of annual inspection and fire engineering costs on the market?
The following are the general market reference ranges, which are not fixed prices and are actually subject to formal "ation after site surveys:
- Annual inspection : Small shops are more than ten times different from large business sites, generally by number of devices and type of system.
- fire engineering: The costs include design fees, plans and application arrangements, material materials, installation of manual work, testing and acceptance inspection.
- remedial work: alternatively, by actual replacement of components and quantities of pharmaceuticals.
We provide free initial advice and can make a budget assessment on the basis of a snapshot, then arrange for confirmation at the gate.
What projects should be included in fire engineering?
Completedfire engineering "It should be specified that:
- The site survey results and programme descriptions;
- fire protection system designand plans;
- (b) The specification, branding and quantity of devices and material;
- Installation of manual work, construction time and duration;
- Testing, testing and acceptance inspection cooperation;
- (a) The issuance and presentation of the certificate;
- (a) The option of sequestration and maintenance;
- A clear listNot included(e.g., daylight rehabilitation, electricity supply, earthwork).
" Is it discovered that an additional fee would be incurred for construction?
If the construction project is outside the original scope of "ation " (e.g., when the site survey has not been carried out on an astronomical basis, concealment problems are found or customer change spacing designs), it will normally be treated in writing with a reduction in the number of accounts. The practice of reducing disputes is to keep on-site inspections as open as possible during the site survey phase and to include in the contract an additional deduction procedure.
V. Fire extinguisher annual inspection, inspection and exchange of medicines
What are the requirements of fire extinguisher annual inspection and fire extinguisher for medication?
Such fire extinguisher shall be carried out in accordance with the Fire Services Department ' s Code of Conduct for Inspection, Testing and Maintenance of Minimal Fire Service Facilities and Equipment and Inspection, Test and Maintenance of Devices and Equipment12-month test,All fire extinguisher must be tested for pressure within five years。 If the inspection is not qualified, it shall be arranged for replacement of medicines, repairs or replacements.
What are the projects visited by fire extinguisher?
- The pressure sheet is whether or not the syringe is in its normal scope, and whether there is any leakage.
- There is no corrosion, trap or change.
- Lead, safety needle, labelling and last inspection date.
- spraying, spraying, chicken tubes are old, fracture or cemetery.
- Pharmacological condition (whether the dry powder) and weight.
- Whether the location is easy to use, whether or not the goods are hanged and whether the walls are fully aligned with the markings.
- The type of fire extinguisher corresponds to the risk on-site (seater, electricity and warehouse requirements vary).
What are the differences between switching, pressure testing and whole replacement?
- Fire Extinguisher Servicing
- Pharmacies have been used, blocked or deactivated and repackaged with ad hoc fire extinguishers.
- Pressure tests (hydraulic test)
- In accordance with the Code, all fire extinguisher is subject to pressure tests within five years to confirm that the structure of the body remains safe.
- Replacement
- Direct replacement is more reasonable when a grave corrosion, change, spare parts are parked or maintenance costs are close to new purchases.
Would fire extinguisher never be used, nor should it be subject to an annual inspection?
To do so. Pressures and pharmacies change over time, temperature, humidity and shock, as well as corrosion of the body, so the code requires testing every 12 months and testing for pressure within five years. Annual inspection records and FS251 also need to reflect the actual status of hand-held equipment.
How much fire extinguisher and fire blanket should be allocated to food premises?
According to Fire Services Department, fire safety at licensed stations and food industry information:
- In the general food premises, each 100 m2 of seats will require a 9 litres of water packing or 5 kg of dry powder fire extinguisher. Water is applied to woodwork, textiles and paper fires, which are used for electrical equipment, flammable liquids or metal items; The dry powder applies to most of the flames.
- (b) The general need for a 4.5 kilogram of carbon dioxide fire extinguisher per three helmets, depending on the size and location of the head; Carbon dioxide can be an abhorrent and should be withdrawn from its use to unattended areas.
- A 1.44 square meters of fire blanket are generally required for each blow, depending on the size and location of the blow.
The actual configuration is still subject to confirmation by location and by Fire Services Department. Relevant product seeFire safety products。
What is the choice of different colours or types of fire extinguisher?
The key to the prototype is on-site fire: water-based wood, paper, textiles; Dry powder cover is most extensive, including flammable liquids, metals and electrical equipment; Carbon dioxide applies to electrical equipment, flammable liquids, sophisticated instruments and important documents, or fire in closed areas. The palm oil tanker is supplemented by fire blanket and automatic fire extinguishment systems. The type of error is not only ineffective, but more likely to expand the fire or create a risk of electric shocks.
Could fire extinguisher be purchased online?
Technically available purchases, but three points are to be left: the product specifications are subject to Hong Kong acceptance criteria; The maintenance, repair and inspection of hand-held equipment falls within the scope of work of the registered contractor for level 3; Annual inspection will remain a defect if the source, specifications or quantity of the device does not meet the requirements. It was suggested that the contractor should supply and register together, and that future conversions and records would be more smooth.
VI. Annual fire safety inspection remedial work and deficiencies
What does the annual fire safety inspection remedial work include?
Frequent remedial work projects:
| Shortcomings | Common treatment |
| fire extinguisher under pressure or obsolete pharmacies | Economies, pressure tests or replacements |
| Detector failure, accumulation and location | Cleaning, replacement, design repositioning |
| fire alarm bell unsound or inadequate | Renovation lines, replacement of clocks, adjustment of subsectors |
| emergency lighting inadequate power time | Replacement of batteries or lamps |
| exit sign damaged or desecrated | Replacement of lamps, removal of stoves |
| sprinkler head thick, mute and corrosion | Replace sprinkler head, adjust the flower opening |
| Underwater pressure or leakage | Refurbishment group, valves, pipes |
| door cannot be closed on its own | Repair of closed door, five gold and gate |
Would the defect be remedied immediately?
It should be treated at a risk level. Projects that affect immediate fire extinguishing or evacuation capabilities (e.g. alarm void, fire extinguisher untouchability, export instructions blanket, sprinkler control closure) should be prioritized; Other items such as chicken colours, crust minor corrosion can be dealt with in the same instalment. In any event, the legislation requires the installationTimeMaintaining an effective operational condition and the risk of long-term setbacks is high.
Should remedial work require re-examination?
Need. The system should be retested and the response normal, after which FS251 reflecting the actual situation was issued. If the certificate still includes an unprotected project, subsequent licence or inspection may be pursued.
Can only be checked, remedial work done and alternative home searched?
Could, but three points should be noted: the remedial work must have a registration level covering the system; Once completed, the test shall be retested and certified by the appropriate party; Separation of two doors often leads to inconsistency between responsibility for defects and records. If price considerations are taken into account, it is suggested that the prosecution be required to report a bath examination and remedial work in two sets of prices for comparison.
VII. OPERATIONS, FACILITATION AND TRANSFER PROTECTION system
What fire engineering is needed to open up?
Depending on the type of property industry, area, use and year of construction, common basic requirements include:
- fire detection and alarm devices ( smoke detector, hand-held fire ⁇ , fire alarm bell);
- emergency lighting and exit sign ;
- (b) Shand fire extinguisher, by area and by use;
- Partially required fire hose reel or automatic sprinkler system ;
- The door is complete by means of fires, fire-fighting and fire.
Additional specific fire safety standards for catering, education, dormitories and storage of dangerous goods recommendedPending the signing of leasesThe current status of the unit was first assessed, and it was not possible to identify major changes after entry.
What fire safety projects should be checked before renting a shop?
- List of existing units and last FS251 (with or without expiry).
- Fire Services Department or ISA notification, fire safety direction was not completed.
- sprinkler and detector coverage are compatible with your spacing plan.
- Do you have enough access to the fire, the number of exports and the width.
- Whether or not the dam is part of the old building and is subject to Chapter 502 or Chapter 572 (which may be costed to improve engineering amortization).
- Allocation of responsibilities for fire engineering, annual inspection and remedial work in leases.
Is it necessary to change the flower or spacing, and to make a fire protection system?
Need. Changes to strokes, spacing, wind tubes or additional rooms would affect sprinkler ' s water cover, the range of detectors, fire alarm bell spectacularity and the visual nature of export instructions.fire protection system changeThe construction of a registered fire service installation contractor is required and will be certified upon completion; Not addressed is often cited as defects in annual inspection or inspection.
What is the attention to be paid to building baths, cabinet buildings or stores?
The additional floor or closed space would create new protected space, usually requiring additional sprinkler head, detectors, police clocks and lighting, as well as checking whether the escape route remained in compliance. Such changes often involve the requirements of NASA, and it is suggested that the contractor should coordinate with the designer at the plan stage.
Can the water head or detector be temporarily sealed during the refurbishment?
Temporary protection for the defence during construction is a common practice, but it must be recorded, head-in-charge, demolition time frames and removal and testing immediately after completion of construction. The most common serious problem is that, after completion of the renovations, it is forgotten to dismantle the protection of rubber bags or shielding and that the system is in deactivation.
Would the repairer be able to perform fire engineering on his behalf?
It is not possible, unless the contractor itself is a registered fire service installation contractor covering the relevant level. The installation, maintenance, repair and inspection of fire service installations shall be carried out by the registered contractor. It is common practice for the dressing agents to be responsible for civil construction and day flowers, fire safety contractors for installations and evidence, and both parties to coordinate their positions at the plan stage.
VIII. Fire safety plans design and approval
What are the fire safety plans separate from construction?
The plans are designed blueprints that indicate the location, specifications and quantity of all fire service installations to be submitted to Fire Services Department in accordance with relevant codes and procedures; The construction is to be carried out in strict accordance with accepted plans and using products that meet the specifications. Both must be consistent, otherwise the acceptance inspection would not be noted.
What forms are the fire service installations plans to be submitted?
Fire Services Department information: use of building fire service installations plans FSI/314A (a) Form; Approval of fire service installations plans submitted under Chapter 502 or Chapter 572 FSI/314B or FSI/314C Provide complete and accurate information on the table (project address, company name, etc.); The Safety (Industry Buildings) Regulations, Chapter 636, are subject to FSI/314D The table provides information.
In addition, Fire Services Department circular information indicates that the submitted fire service installations plans are subject to a certificate signed by the Authorised Person and the designated contractor/adviser of the fire service installations (FSI/314), while the initial inspection request for fire service installations is made FSI/501 The table is presented to the Director of Fire Services Department. The actual application forms are to be confirmed by the regulations and nature of the works to which they belong.
How long are the plans to be approved?
The approval time is subject to the nature of the work, the integrity of documentation and the complexity of the system. In the case of pyrotechnic control systems (i.e. building lift pressure, static or mechanical ventilation and ventilation/conditioning control systems), Fire Services Department ' s common problem information indicates that the general situation is not less than 12 weeks.
The most effective way to shorten time is through the first submission of a ready-to-face document (the owner ' s consent, the relevant approval plans, enabling documents) and the reconciliation of the details of the plans by experienced contractors and the reduction of back-to-back round-trip.
Is the plans acceptable?
In accordance with the Fire Services Department ' s Chapter 572 plans, approval process information and acceptance or approval of cases may be modified for fire service installations contractor or engineering consultant as required. For major changes involving the number, design or location of the devices, the revised plans should be resubmitted in accordance with the procedure and the post-construction supplements should be prepared.
What are the plans that have not been approved?
Under the Fire Services Department process, the contractor or the engineering consultant were notified of the results with the approvals and the owner ' s legal team or owner would have received notification of the outcome. The contractor shall amend the plan with the approval opinion and submit it.
Who is responsible for preparing fire safety plans?
Generally, the design and submission of a registered fire service installation contractor or engineering consultant is to be supported in part by the Authorised Person as proof of consistency between plans and construction plans. The role of the owner is to provide enabling documents, construction plans and use information, and to confirm whether the design fits into operational requirements. Related servicesFire engineering。
IX. Fire safety acceptance inspection and fire safety certificates
How long does fire safety acceptance inspection take?
Fire Services Department indicated that the vast majority of the entire process (by applying, verifying all plans, completing acceptance inspection and finally issuing fire safety certificates) at present could be completed 52 working daysCompleted. Fire Services Department 2025 March 13Establishment of a one-stop acceptance inspection office for the construction of new fire safety facilities (Operational Safety Acceptance Inspection) to reduce the overall acceptance inspection time for regular projects of general building size by one third through science and technology applications, hyperlinking and streamlining processes 35 working daysCompleted; The objectives of the public housing project are 22 working daysCompleted.
How does the integrated operation of fire safety acceptance inspection?
(a) In line with Fire Services Department and public reporting, the Office serves as a collaborative platform to deepen communication with building practitioners and registered fire service installation contractors; The measures included the assignment of case directors to check the list of documents within a short time after receipt of applications, arrangements for acceptance inspection plans and details, pre-improvement of acceptance inspection schedules, and the establishment of specialized e-mails and hotlines to provide support to industry.
fire safety certificate FS161?
FS161 issued by Fire Services Departmentfire safety certificate。 According to the Fire Services Department ' s fire service installations plans for approval of process information, the plans will issue a fire safety certificate (F.S. 161) to the contractor of the fire service installations or the engineering consultant, and the owner ' s legal team or owners will receive notification of the results.
In the case of food premises, Fire Services Department issued a fire safety certificate as one of the prerequisites for the applicant to have complied with the various fire safety requirements and for the issuance of a licence at the general food premises or minor food premises.
What is the acceptance inspection unsatisfactory?
The general process is to consult with the contractor after receipt of the identified defects project, revise as required, retest and arrange for a review to confirm that the certificate was issued only after completion. Common reasons for non-acquisition include the incompatibility of installation sites with plans, inadequate number of devices, failure to test systems (shortfall of water pressure, dysfunctional detectors), use of unspecified products and poor quality of construction.
Methodologies for risk reduction: full-scale construction by plan, completion of comprehensive testing and retention of the test record prior to application for acceptance inspection.
What documents should be prepared prior to acceptance inspection?
Generally, the relevant supporting documents, specifications and certifications of installations and material, systems test records, as well as the applicable FS251 or FSI/314 series are accepted for fire service plans, contractors and Authorised Person. The specific list is based on a case-by-case application of the regulations and Fire Services Department requirements.
X. Fire protection system installation and design
What is the design of a fire protection system to consider?
Core considerations include: site use and fire risk, area-to-building, number and evacuation routes, ceilings and structures, spacing, coordination with other electrical systems (electricity, ventilation, water pipes), and related codes and regulations. The good design will set aside maintenance corridors and future changes to flexibility, reducing the cost of each refurbishment.
How long is it generally necessary to install the fire protection system?
Small shop detection, alarm , lighting and fire extinguisher are usually completed one to two weeks; The medium-sized works involving sprinkler pipe, aluminium group or gaseous fire suppression system need to take longer and be in line with the order of flowers, tubes and electrical works. The overall timetable must also take into account plans for approval and acceptance inspection arrangements and recommend early commencement.
Sprinkler system emplacement with sprinkler head, what is the attention to be given to replacing?
(a) The direct impact of dams on the distance between sprinkler ' s head and flowers, lamps, shoes and spacing; Replacement shall be by using sprinkler head with the same specifications (response speed, fluid temperature, direction) and after completion test control of aluminium and flow alarms. In particular, the warehousing takes note of the fact that the dumping height is not close to sprinkler head.
What is the appropriate place for gaseous fire suppression system?
FM-200 systems, CO2 systems etc.gaseous fire suppression systemSpaces that are often used for unsuitable water, such as server room, electricity wards, data centres and sophisticated equipment rooms. The installation must be accompanied by a combination of alarm links, delays, warning signs and personnel evacuation procedures; Daily inspections focus on steel bottle weights/pressures, piping and spraying conditions and associated functions. Carbon dioxide can be an abhorrent, and the safety of personnel must be ensured when used and tested.
What is the automatic fire-fighting system for kitchens?
It is an automatic fire-fighting device designed specifically for the helm and oil blowing areas, with a spray cover of appliances and gas pumps, which cut off fuel supplies simultaneously. In accordance with Fire Services Department general (speed meals) food premises fire safety standards, the location of all cooking and oil-burning food activities is additional to the installation of automatic sprinkler system, which must conform to the UL-300 test set by the United States Security Detection Laboratory Corporation (UL).
What are the common problems with emergency lighting and exit sign?
The most common is that battery ageing leads to inadequate power time, new spacing or branding of lamps, inconsistent orientation instructions with the actual escape routes and non-replacement of refurbishing lights into emergency electricity sources. Annual inspection will be carried out with a plating test, and replacement of battery or lamps should not be required. Food premises using an independent battery emergency lighting system are required to obtain a test report or checklist of the system, together with an effective FS251, according to Fire Services Department information.
XI. Fire equipment maintenance and fire protection system
What are the differences between fire equipment maintenance and annual fire safety inspection?
The annual inspection is the statutory check required by Chapter 95B, and is issued at least once every 12 months FS251.fire equipment maintenance(orfire service installation maintenanceIt is additional preventive work such as regular cleaning detectors, testing of bands, inspection of battery and fittings, recording stress trends. Maintenance is well done, and the number of defects in annual inspections and costs for remedial work are typically significantly reduced.
What is the general inclusion of maintenance contracts?
Common elements: number and scope of periodic inspections, annual inspection and certificate delivery arrangements, emergency call response time, inclusion of basic consumption materials, reporting and record formats, fees and modes of recording. The contract shall be preceded by a confirmation of which projects are contracted, which are counted and an annual inspection reminder mechanism due.
What are the frequent mistakes in fire alarm bell?
Frequent factors: detector accumulation, exposure to wet gas or oil cigarettes, old-line or poorly exposed batteries, mainframe backup batteries, location of the detector close to the kitchen or shop. The approach is to check the mainframe incident record, district-by-sector testing, cleaning or replacement of detectors and repositioning where necessary. The long-term segregation of the system or the dismantling of the detector, which renders the entire alarm system ineffective.
How do fire hose reel underwater pressure?
The normality of fire pumps and cumbersome operations, control of the lithium and power sources, valves, leakage or blocking of the pipe, water tankers and repair or replacement of components as a result is subject to a gradual check. This falls within the scope of the work of the second contractor, which is then retested and recorded water pressure data.
How does sprinkler address water leakage or misspray?
The Management Service should be immediately informed that the relevant sub-sector control plutonium is closed to reduce water pumps in accordance with the procedure and then checked by a registered contractor (the sprinkler head was hit, corroded, temperature anomaly or installation problem), replacing the component back-up system and testing. FocusResponses as soon as possible: The control of the plutonium has been closed for a long period of time, while the area is deprived of protection.
How long should the fire pump be examined?
The statutory minimum requirement is for a registered contractor to check at least once every 12 months, but the sub-cluster is equipped with mechanical equipment, which makes it easier for the long cycle to cover such issues as sealing dumps, batteries and control of malfunctions, so that well-managed property usually arranges more frequent routine operational tests and keep records. The actual frequency is tailored to the condition and management needs of the equipment.
Are emergency maintenance services provided?
XII. Legislation on the old building, fire safety direction and penalties
Which buildings are regulated by the Safety (Buildings) Regulations (Chapter 572)?
Chapter 572 came into force on 1 July 2007 and is applicable to the initial submission of construction services supervisory approvals on or before 1 March 1987, or their construction plans on 1 March 1987Integrated-purpose buildings(Commerce building) andAccommodationIt is required that fire protection be upgraded to modern requirements.
(a) Instruction of the requested fire service installations and equipment, including automatic spraying systems, fire safety and shrimp systems, hand-held fire alarm system, emergency lighting and mechanical ventilation systems, according to government information; The safety of fire includes avenues for evasion, building fire-resistant structures and fire safety and access to rescue.
What commercial buildings are regulated by the Safety (Commerce) Regulations (Chapter 502)?
Under Chapter 502, where the building has been built for office, operation, trade or any recreational purpose or is being used for that purpose and the building has been completed on or before 1 March 1987 or its construction engineering plan was first submitted to the Authority for supervision of construction services on or before that date.Specify commercial buildings。
Are there special Fire Safety Ordinances in industrial buildings?
Yes. The Safety (Industry Buildings) Regulations (Chapter 636) contain corresponding authorization requirements for fire service installations plans, and Fire Services Department provides a checklist to indicate that complete and accurate information is required in the FSI/314D form. Industrial building is under way for owners, legal missions and tenantsindustrial building fire safetyUpon improvement or addition, the applicable regulations shall be recognized first.
What is the safety of fire?
It is the circular issued by Fire Services Department and the Office of Buildings to owners or occupants of the target building, in accordance with the relevant regulations, indicating the fire safety improvement works to be carried out. Depending on the case of individual large dams, fire service installations and equipment (e.g. automatic spraying, fire safety tumours, hand control fire alarms, emergency lighting, mechanical ventilation) as well as fire safety construction (access to escape routes, fire-resistant structures, fire safety and access).
What are the consequences of not complying with the fire safety direction?
According to Chapter 572, the owner or occupier is guilty of having no reasonable justification and not complying with the fire safety direction. The maximum fine for non-compliance with the instructions was increased from step 4 ($ 25,000) to level 6 (US$ 100,000), and the daily penalty for continuous non-compliance was raised from $2,500 to $10,000.
In addition, according to the Government, if the owner or occupier did not comply with instructions within a reasonable time and failed to provide reasonable justification, the executive authority may apply to the court of decision for compliance with fire safety orders; Failure to comply with an instruction or the order is a crime punishable by a fine.
What should be done to receive fire safety guidance?
Order of recommendations:
- The project and the completion period for checking the instructions on a case-by-case basis.
- Author appointed registered fire service installation contractor and, if needed, Person to assess the status.
- Preparing programmes, plans and budgets for consideration by the Owners ' Assembly or management.
- Processed submission of plans, construction, testing and placement acceptance inspection.
- All certificates and records are maintained, used for future search and annual inspection comparisons.
Time is often the largest source of pressure, and assessments are beginning early, with space comparison programmes and phased construction.
XIII. Safety requirements for fire at various sites
What fire safety documents are required to apply for food premises?
According to Fire Services Department, the applicant is required to obtain the following supporting documents for the issuance of a fire safety certificate (as applicable):
- (b) The copper issued by registered fire service installation contractor is in accordance with the certificate of security (FSI/314A or FSI/314B) and/or certificate of Fire Service Installations and Equipment ⁇ (FS251);
- (b) The acquisition of hazardous items licence or letter of approval if dangerous goods exceeding the amount of exemption are stored or liquid dangerous products using a storage facility;
- If an independent battery emergency lighting system is installed, the test report or checklist of the system shall be obtained together with an effective FS251;
- In the case of polymer rubber soft furniture, invoices indicating that they meet combustion criteria and copies of test certificates issued by the accreditation experiment are required.
On the process, the applicant first referred the application and design plan to the UNCED licence team, which in principle would be accepted and then referred to Fire Services Department ' s fire-proofing subsector office.
restaurant whose circumstances must be installed sprinkler system ?
Safety standards for fire safety at Fire Services Department general (speed meals) food premises: the location of the premises exceeds the size of the area where it is located 126 m2(b) The need for fire safety sprinkler system ; Excess of area 230 m2Fire safety sprinkler system is also required. In addition, all helmets and locations used for oil-invading food activities require additional automated sprinkler system with automatic control fire/fighting systems that meet the criteria of UL-300.
The higher-risk food premises category (e.g., firewood gardens) also provides specific criteria for the actual requirements to be recognized by prescription category.
What is the attention to be paid to the design of an open kitchen?
Open designs reduce the separation of kitchens from restaurants, and the heat, cigarette and oil smoking generated by meals are more easily accessible to detectors and sprinkler, while influencing the spread path of fire. The design phase will need to assess sprinkler ' s coverage, the selection and location of detectors, the configuration of gas pumping and fire extinguishment systems, and confirm compliance with applicable food premises fire safety standards.
What is the focus of industrial building and mini-storage fire safety?
Focusing on spacing and filters: high density spot detectors and sprinkler ; Excessive reservoirs will dampen the water; The passage is occupied by the goods, which may affect evacuation. In addition, industrial building often involves changes in uses (e.g. conversion to work rooms, warehouses or extensions), it is necessary to confirm whether existing devices are still applicable and to take note of the relevant requirements of chapter 636.
What are the special considerations of institutions, schools and clinics?
The common densities of such sites are weaker or concentrated users ' evacuation capacity, and alarms are therefore particularly important, emergency lighting reliability, unfettered access and staff response procedures. In addition to the statutory annual inspection, it is recommended that daily inspections be strengthened (e.g. monthly self-censorship of fire extinguisher seal lead and whether export gates are locked) and records maintained.
Why do the data centre and server room extinguish the fire?
Because water caused secondary damage to electronic equipment. Gaseous fire suppression systems such as FM-200 or CO2 can contain combustion without water, suitable for server room, power kitchen and sophisticated equipment rooms. The design will be designed to deal with room sealing, leakage, hybrid control and personnel evacuation alerts; CO2 In particular, the system is subject to interest-bearing risks.
What are the fire safety maintenance of residential dams and residential estate?
Common projects in the public sector: fire hose reel and fire safety baths, kitchens and water tanks, hand-held fire alarm system, emergency lighting and export instructions, building door fire, common area fire extinguisher, and automatic spraying and mechanical vent systems (beyond buildings). Legal missions or management companies are usually arranged in the form of annual maintenance contracts and are co-opted with annual inspection and FS251. Related servicesfire protection system maintenance and annual inspection。
What is the risk of fire safety in sub-rooms?
The main risks are the change in the original design: spacing of detectors and dams, dysfunctional effects of corridor vapours, increased power burdens, escape routes through other rooms. The approach is to re-examine detection and alarm coverage, lighting and direction, bandwidth, and to confirm that the overall changes comply with the relevant legislative requirements.
What are the different safety requirements for hazardous stores?
Depending on the nature of the material stored, it usually involves specialized fire extinguishers, ventilation, separation and stock limits; If a dangerous item exceeds the amount of the exemption, it is also necessary to obtain a licence or authorization from the Fire Services Department for the storage and use of hazardous items. Such sites are proposed to conduct risk assessments before renting or alterations are made, avoiding the extremely high cost of post-retroactivity changes.
XIV. Selection of fire engineering companies, contracts and payments
How can fire engineering companies be selected?
Five substantive inspection points:
- Registration qualifications:: Holding Fire Services Department registered fire service installation contractor qualifications and level coverage of your system.
- Same experience: Whether property has been treated for the same purposes ( restaurant, industrial building, yards, residential estates are difficult).
- " TransparencyNumbers, specifications, inclusion plans, acceptance inspection and presentation of certificates by item.
- One-stop capability: Coherence of design, construction, acceptance inspection to annual inspection maintenance.
- Follow-up supportEmergency maintenance response, annual inspection reminders and record-keeping.
Police No.: " Not less than the same practice does not specify scope, cannot provide a certificate of registration, requires full advance payment, promises unreasonably completed or approved time.
Can fire safety equipment be purchased for themselves, and can it be installed?
No recommendation. The device must meet the accreditation specifications, while the contractor is responsible for the construction and certification of the system as a whole; Self-purchasing devices, where they are not specific, lack of authentication documents or are incompatible with existing systems, are often noted when acceptance inspection or annual inspection is eventually re-procurement. If the brand is biased, it would be preferable to request that the contractor be replaced with procurement and identification specifications.