Hong Kong Fire Safety Legislation and Requirements

2026-03-07 Final update 2026-09-22 fire safety information Grand United Eng., Co.

Hong Kong fire safety regulations are made up of six core legislation dealing with the three main lines for the maintenance and annual inspection of aluminium contractor ' s qualities, and the improvement of the old building. The present document specifies the scope of application, the law enforcement procedure and the scope of application according to regulationCurrent penaltiesIt also sets out the respective responsibilities of owners, business owners, management companies and tenants. (a) The content is organized in accordance with the text of the regulations in force, the Fire Services Department and the Board ' s published information; In relation to whether a particular building is the target building, please refer to the relevant department or to usfire safety adviserVerification.

I. Overview of Hong Kong fire safety legislation framework

VI. Core legislation

Hong Kong Core fire safety legislation and regulatory content
legislationRegulatory content
Chapter 95 Safety and Safety Regulationsfire safety maternity law, which authorizes the establishment of subsidiary regulations and the empowerment of Fire Services Department.
Chapter 95A, fire safety (container contractor) Regulations(c) The registration system for fire service installations contractor, which is registered at levels 1, 2 and 3.
Chapter 95B Firearms Safety (Equipment and Equipment) Regulations(a) The owner is required to remain in an effective state of operation at the time of the installation; At least once a 12-month period is examined by the registered contractor; The contractor is required to issue FS251 within 14 days of completion and send a copy to Fire Services Department; Non-registered contractor shall not be placed in the premises, maintained, repaired or inspected fire service installations or equipment.
Chapter 502 Safety (Commercial Services) RegulationsIn order to identify commercial premises and identify business buildings, demand or improve fire service installations and fire safety construction.
Chapter 572 Safety (Buildings) Regulations(b) For designated integrated-purpose buildings (commercial building) and residential buildings; The year 2002 was passed by the Legislative Council in July, with effect from 1 July 2007.
Chapter 636 Safety (Industry Buildings) RegulationsTargeted industrial buildings; Entered into force 19 June 2020.

There are two other key documents at the technical level: Fire Services Department ' s Code of Conduct and Inspection, Testing and Maintenance of Equipment (the revised version of 1994 is applicable to fire service installations and equipment provided or improved under Chapter 502 and Chapter 572) and the Board ' s Code of Safety for Buildings 2011 (2024).

Date of separation 1 March 1987

Chapter 572 applies to integrated-purpose buildings and residential buildings that were either on or before 1 March 1987 and submitted construction plans; Chapter 636 is applicable to the target industrial buildings that were laid down on or before that date, or for the first time before that date or prior to the submission of construction plans to the supervision and approval of construction services. The date reflects the separation of safety standards at the time of construction: the buildings that were subsequently constructed are generally designed on a more new basis, while the old building is to be gradually upgraded through the above-mentioned special regulations.

Retention: the length of the building is not the only judgement. Chapter 502 lays down business premises that are not conditioned by the year of landing, but are determined by the type of commercial activity and the size of the general building. Therefore, the applicable requirements may vary in different locations within the same building.

Division of labour between the two executive authorities

Fire Services Department Chief
Implement regulations on fire service installations or equipment, including approvals, acceptance inspection and law enforcement. For inquiries: 2272 9112 (Sitecture Improvement Support Centre, e-mail fsdbisc@hkfsd.gov.hk).
Administrator, Board of Directors
Enforcement of regulations on the planning, design and construction of buildings (safety building), such as the introduction of fire routes, fire-fighting separations and structural resistance. Referral: 2626 1616.

Both can direct fire safety/improvement of fire safety on the same building or jointly. The first step after the receipt of instructions should be to identify which party, otherwise programmes and budgets would be easy to make mistakes. Substantive follow-upSubstantive guidance on scope of services: improvement of regulation in the old building。

II. Chapter 95A: registered fire service installation contractor class 3

The fire service installations are regulated. Chapter 95A establishes the contractor ' s registration system, in grades 1, 2 and 3 (commonly known as RC1, RC2, RC3); By chapter 95B,Non-registered contractor shall not install, maintain, repair or inspect fire service installations or equipment at any place。

registered fire service installation contractor Class 3 scope
LevelQuorum of workCommon systems
Level 1 (RC1)Devices, maintenance, repairs and inspections of electrical or other instruments to detect cigarettes or fire, and fire service installations or equipment (except hand-held devices) that are alarmed or otherwise warningd.fire alarm system, cigarettes and heat detector, mobile alarms, fire alarm bell
Level 2 (RC2)Devices, maintenance, repair and inspection of fire service installations or equipment (except hand-held equipment), including plumbing and fittings designed or modified for the transmission of water or other fire extinguishers, or other types of electrical devices specified in level 1.automatic sprinkler system, fire safety tumours and copper, fire pump and pressure, gaseous fire suppression system plumbing, automatic fire extinguishing systems, smoke-free systems
Level 3 (RC3)Maintenance, repair and inspection of handheld equipment.Fire extinguisher, fire blanket

It is common mismatch that the first level is responsible for gaseous fire suppression system. gaseous fire suppression system, involving pipe and accessories for the transmission of fire extinguishers, falls within category 2; Its detection and association component relates only to level 1. Similarly, emergency lighting is not the same type of device and should be judged by the nature of the actual installation.

It was recommended that the registration level and status of the nuclear contractor be checked by Fire Services Department, with a request for registration information. Detailed description of the levelfire safety knowledge: RC1/RC2/RC3 division of labour。

III. Chapter 95B: annual inspection, FS251 and electronicization

Three statutory figures

Effective operational status
The owner of fire service installations or equipment is required to remain in an effective state of operation at the time of the installation.
At least once every 12 months
The device must be checked at least once every 12 months by the registered fire service installation contractor, i.e. what is called by the industryAnnual Fire Safety Inspectionorannual inspection of fire service equipment。
14 Date of communication
The contractor is required to issue FS251 Certificate of Fire Service Installations and Equipment within 14 days of completion of the installation, maintenance, repair or inspection and send a copy to the Fire Services Department; Failure to comply with statutory requirements may be prosecuted for violations of the relevant legislation.

In the area of fire extinguisher, according to the Fire Services Department code, such fire extinguisher should be tested every 12 months, whileAll fire extinguisher must be tested for pressure within five years。

Two common misunderstandings are to correct: one, FS251 is the plutonium certificate issued by the contractor and not an annual inspection report completed by the owner; Second, fire extinguisher ' s pressure test year is 5 years, not 5 to 10 years.

FS251 Full electronicization

Fire Services Department ⁇ Certificate of Fire Service Installations and Equipment (FS251) Online Transmission System operated on 1 April 2019, with contractor able to prepare and submit certificates, record-keeping at the Platform and may be submitted through the last volume of Excel statements. With the consolidation of the system, Fire Services Department has fully implemented FS251 e-transformation from 1 July 2026: contractor enters a building address within the system, fire service installations category, inspection results, damage and restoration status to be submitted for smart convenience or upon completion of electronic signature by Hong Kong Postal Electronic Certificate, which automatically produces an official electronic certificate with a counterfeited dividing code. Fire Services Department has also strengthened the regulation of contractors, including by expanding the size of spot checks for annual inspection checklists to approximately three times, covering about five active contractors.

For owners and management, this represents a record that is in situ and is more easily identifiable, while electronic certificates can be authenticated by a two-dimensional test. Complete process and remedial work arrangements are availablefire protection system maintenance and annual inspectionandfire engineering services: maintenance, annual inspection and remedial work。

IV. Chapter 502: Safety of commercial premises

Scope of application

Establishment of commercial premises

General surface areaOver 230 m2It is also used as a repository for the designation of commercial activities, including banking (except for businessmen ' s banks), outposting, jewellery or gold operations with security zones, supermarkets, mega supermarkets or consortia, and commercial sites.

Specify commercial buildings

This refers to commercial buildings as defined by regulation (as used for office, operations, trade or recreation purposes). Whether a particular building is the target building shall be verified to Fire Services Department or to the Board of Tenure.

Projects that are often required to provide or improve

fire service installations and equipment

  • Automatic spraying system ( sprinkler system ).
  • Automatic discontinuation of facilities for mechanical ventilation systems.
  • fire safety and copper systems.
  • Holders fire.
  • Shanded fire extinguisher.
  • Emergency lighting system and export instructions.

Safety construction

  • Provide sufficient fire access to allow users to escape.
  • Provide sufficient access to fire safety personnel for fire extinguishing and rescue.
  • The provision of fire-proof measures to prevent the spread of fire and smoke (e.g. fire door, fire-fighting).
  • (c) Ensure that the structure of the building is resilient to fire.

Law enforcement procedures

  1. Visits: Fire Services Department, inspectorate with the Office of the Board of Tenure Targets or buildings.
  2. Issuance of instructions:: To issue fire safety direction to owners and/or occupants or improve fire safety direction, indicating the need to improve projects and deadlines.
  3. Application orderIn the event of non-compliance, the executive authority may apply to the court for compliance with a fire safety order or an improvement in fire safety orders.
  4. Restrictions on the use or prohibition of use: In serious cases, a restraining order or a restraining order may be applied to restrict or prohibit the occupation of the premises.

Correspondence of regulations to engineering arrangementsScope of services: fire safety in old buildings。

V. Chapter 572: Integrated and residential buildings

Entry into force and scope of application

The regulations were public consultation in 1998 and passed by the Legislative Council in July 2002 and are self-reliant1 July 2007Entry into force applies to integrated-purpose buildings (commercial buildings) and residential buildings that were either landed or submitted for construction plans prior to 1 March 1987. The implementation is roughly two-pronged: the first tour of the integrated-purpose buildings regulated by the Regulations, and the subsequent extension to the residential building. Whether a particular building is the target building shall be examined by Fire Services Department or by the Board of Buildings.

Common improvement projects

Fire service installations in the public sector

  • fire hose reel system.
  • Hand-held fire alarm system.
  • emergency lighting.
  • Export instructions.
  • Shanded fire extinguisher.

Safety construction

  • fire door (buildings, astronomy, etc.) and maintenance of its own closure function.
  • Flame access and lifts are maintained.
  • Fire-resistant separating and structural fire-resistant improvement.

The penalty has been increased (a significant update)

Chapter 572 ' s penalties have been significantly increased as a result of the revision, which is a point where many old information has not yet been updated:

  • Owners or occupiers have no reasonable justification to comply with fire safety direction: once convictedLevel 6 fines (up to 100,000 yen)and may impose an additional daily penalty for the continued non-compliance with this instruction $10,000(Percentage 25,000 yen and 2,500 per day for step 4) was amended.
  • Failure to comply with fire safety orders: penalties $200,000and may impose an additional daily penalty for the continued failure to comply with this order $20,000。
  • The building or its related parts are occupied without reasonable justification for breach of the prohibition: a fine of US$ 250,000 and imprisonment of 3 years, and an additional amount of US$ 25,000 per day for this violation.

The real impact on junta and management companies: the cost of delaying improvements has risen significantly and is accumulated daily. It was suggested that the improvement of the programme be phased out and included in the budget for the fiscal year, rather than the end of an instructional period.

2026 Alternative programme arrangements

Fire Services Department issued Fire Services Department circular No. 3/2026 on 30 April 2026, which reads under Chapter 572Six or less(b) Integrated use and residential buildings, using the pyrotechnic fire detection system to match fire extinguisher as an alternative to the statutory requirements for the creation of a fire hose reel system and hand-held fire alarm system; The system has also been included in the scope of funding for fire safety improvement projects. According to the Governance Report 2026, Fire Services Department will expand its application to old buildings in seven or more by the end of the year and owners may choose to install alternative traditional fire protection system devices.

VI. Chapter 636: Safety of fire in industrial buildings

Scope of application

Regulation20 June 19(a) Entry into force, which applies to the construction of buildings for the whole or any part thereof that are constructed for the following purposes: factories, industrial operations, warehouses, large stores, or similar industrial premises; It is also required that the construction plans be submitted for the first time on or before 1 March 1987 to the supervision and approval of the construction services. Chapter 636 does not apply if chapter 502 or chapter 572 applies to the building.

(a) The division of labour among the executive authorities: for any fire service installations or equipment in industrial buildings, the executive authority is the chief of Fire Services Department; For the planning, design and construction of industrial buildings, the executive authority is the Administrator of the Board.

Two phases of implementation

  • Phase I: Some 440 plutonium, the target industrial buildings that were either landed before March 1973 or submitted for the first time construction plans, most of which were not installed sprinkler system.
  • Phase II: The remaining 780 target industrial buildings.

The policy objective is to elevate the safety of fire in old industrial building to modern requirements, such as requiring automatic sprinkler system; The receipt of instructions does not represent an imminent danger of fire on the building. Fire Services Department had established the building ' s Support Centre for Improvement in Conencies during the fourth quarter of 2023, providing one-stop full-range support to owners and occupants of targeted industrial buildings, including interpretation of regulations.

Typical risk of old industrial building

  • A large number of flammable materials are stored (papers, feed, packaging, chemicals).
  • Industrial activity generates firefighting (small, cut, grinding).
  • The building is large and spacing, and fires and smoke are easily spread.
  • The original design lacked modern fire service installations such as automatic sprinkler.
  • Decentralization of the right to work makes it difficult to achieve consensus on improvements.
  • Part of the unit ' s non-compliance was converted to other uses and the installation was not adjusted for new use.

Common improvement projects

  • Add automatic sprinkler system and deal with a full suite of water, dams and kitchens.
  • fire alarm system (detectors, mobile alarm points, fire alarm bell).
  • emergency lighting and exit sign.
  • fire safety and fire hose reel system.
  • door is separated from fire prevention, separating the building to smaller areas.
  • The tunnel of the fire and the evacuation stairs have improved, and the tunnels are kept without locking.

The addition of sprinkler is an all-encompassing project involving water, dams, kitchens and utility pipes that cannot be resolved by internal changes in individual units. Decentralized industrial building should be preceded by early consensus-building and phased planning. Individual case practiceProject examples: Industrial Building Compliance Engineering。

VII. Current penalties

The equivalent amount of the fine level is 25,000 yuan, 5 50,000 yuan and 6 minus 100,000.

Three Fire Safety Ordinances are subject to penalties
Non-complianceChapter 502 and Chapter 636Chapter 572
Failure to comply with fire safety direction/improvement of fire safetyLevel 4 fines (up to 25,000 yen) + 2,500 per day for a continuous periodLevel 6 fines (up to 100,000 yen) + per day in duration
Failure to comply with fire safety orders/improvement of fire safetyLevel 5 fines (up to 50,000 yuan) + per day in duration200,000 yen + per day in duration
Occupation of premises in violation of a restraining order or a restraining orderFine 250,000 yen + 3 years ' imprisonment + 25,000 yuan per day for a continuous periodFine 250,000 yen + 3 years ' imprisonment + 25,000 yuan per day for a continuous period

In addition, under Chapter 95B, the owner ' s failure to maintain an effective operational condition of the installation or to conduct inspections on schedule and the contractor ' s failure to submit FS251 within 14 days may be prosecuted for violating the relevant legislation.

This table is a general statement and does not constitute a legal opinion. The amount of the penalty and the applicable provisions may vary as a result of legislative amendments, and the actual consequences of individual cases are subject to facts and court decisions. Ultimately, the existing provisions of the electronic version of Hong Kong legislation and the official documents of the Fire Services Department and the Board of Tenure should be taken into account.

VIII. Fire safety of the licence site

Process of food licence

  1. A licence application was submitted to the Food and Environment Agency.
  2. Fire Services Department issued fire safety provisions on the premises, specifying the fire service installations and arrangements to be provided.
  3. The applicant appoints a registered fire service installation contractor at the appropriate level to design and install.
  4. Post-completion arrangements are made for nuclear inspections.
  5. (b) A copy of the Certificate of Fire Service Installations and Equipment FS251) issued by registered contractor; Part of the situation is also subject to a security certificate (FSI/314A or FSI/314B) and a test report or statement for an independent battery emergency lighting system.
  6. The licence department is issued as a whole.

Frequent misinformation: FS161 is required to obtain FS161 for the posting of a decorator. F.S. 161 YesCertificate of fire safety in construction plans(b) Authorised Person, after the construction plans were approved by the Fire Services Department ' s new engineering department; FS 172, on the other hand, is a certificate for the inspection of fire service installations and equipment in new buildings related to the occupancy licensing process. The licence is generally submitted by FS251. Three comparisonsproject examples: acceptance inspection and certification process。

Electronicization arrangements

Fire Services Department has introduced e-fire safety applications for food permits (including general food premises, small food premises, factory cafeteries, kitchens/food manufacturing plants) and public entertainment sites (including non-drama/theatre, theatre/theatre, with the exception of temporary public entertainment sites), which provide for electronic fire safety and related safety requirements to be transmitted by email; The electronic issuance of fire safety licence and certification system has been rolled out, with relevant fire safety certificates sent by e-mail.

Risk focus of catering sites

  • Storm fires and oil fat accumulation are the main risk source, and pumping gas is subject to regular clean-up.
  • Pumping and ventilation systems are required to meet the relevant fire safety requirements, including automatic shutdown facilities for mechanical ventilation systems.
  • Wet chemical-type fire extinguisher (European standard, category F, United States standard, category K) and fire blanket were configured to feed oil fire.
  • It would be useful to use heat detector in the kitchen area to reduce the erroneous effects of gas and oil smoke.
  • Solid fuels, such as charcoal, are also specifically directed and the applicable requirements should be recognized first.
  • The seat emplacement shall not block export or the breadth of the gateway; Open kitchens are subject to an assessment of sprinkler ' s protection.

Place requirements collatedScope of services: focus of works by industry type。

IX. Eliminating the risk of fire and common violations

Breaking of the flame

It is a typical danger of fire that the stairs of cylinders or single vehicles, corridors are placed, the locks on the door, exports are blocked by the goods or private home. Fire Services Department may issue a request for clearance of fire hazard notices; Under the relevant provisions of the Firearms Safety (Elimination of the Risk) Ordinance, if the fire is repeated at any time within 12 months of the date on which the notification was delivered, it is a crime punishable by a conviction of $25,000 and an additional penalty of 2,500 per day for the duration of the offence.

Failing fire service installations

  • fire extinguisher expired, under pressure or pharmacies.
  • Emergency lighting and exit sign batteries are ageing, and electrical discharge tests do not meet the requirements.
  • Detectors are stoves, contaminated with oil cigarettes or frequencies.
  • door has been dismantled, locked up by wooden sticks for a long time or closed doors have expired.
  • Insufficient hydraulic pressure, leakage of copper or clipping.
  • sprinkler head is wheeled, branded, mounted or tubed.

These projects are at the same time the most frequently listed deficiencies in the annual inspection and are addressed in the direction.fire protection system maintenanceandfire safety knowledge: the most common flaws in inspections。

Unauthorized alterations

The conversion of industrial building units to other uses, shops for drift-off or wardships, houses for commercial use, etc., is often inconsistent with the requirements of new applications (e.g., increased number of evacuation designs, interval detection and clock cover) in addition to possible violations of the Building Regulations and the land contract. Consequences may include a request for suspension of use, prosecution, to be applied for a restraining order in serious circumstances. The change shall be preceded by confirmation of the applicable requirement and handled by a registered contractorfire protection system change。

X. Owners, legal missions and tenant responsibilities

Legislation separately from contractual responsibilities

The fire safety direction may be given to the owner and/or occupier of the building or service, both of which may be prosecuted for failure to comply; However, under Chapter 95B, the duty to maintain an effective operational condition of the installation and to arrange inspections every 12 months is vested in the device. The tenancy clause only delineates contractual responsibilities and does not alter legislative responsibilities.

Tripartite substantive list

The owner is required to know

  • To confirm which regulations are applicable to the property industry (chap. 502/572/636) and whether they belong to the target building.
  • Each 12-month arrangement for the annual inspection of registered contractor and maintenance of FS251 electronic copy and device lists.
  • Detection of damage to installations is scheduled for repair as soon as possible and will not be left to the annual inspection before being processed.
  • The fire safety direction was received and improvements were completed within the deadline, with a record of follow-up.
  • A division of responsibility for fire safety is set out in the lease and a list of devices is attached.

Tenants are required to know

  • Whether pre-lease inspection units and dam installations are fully effective, requesting a most recent FS251.
  • Recognition of the division of responsibility for annual inspection, remedial work and costs in leases.
  • No damage, damage or removal of fire service installations; Sprinkler ' s head and direction light shall not be mounted with the plate.
  • Fire tunnels are maintained and fire extinguisher is not allowed to dump items prior to the prayer.
  • In conjunction with the annual inspection arrangements, contractors are placed on the ground.
  • The operating licence site is required to complete the fire service installations and submit a certificate.

Legal missions and management companies to be informed

  • Develop an annual maintenance and annual inspection schedule with a reminder mechanism.
  • Regular visits to places of public use: access, fire door, sleeping and kitchens.
  • Description to the owner and the household of an inaccessible link or damage device.
  • The process of handling is followed up and documented immediately upon receipt of the hidden complaint.
  • Maintenance funds are set aside for large-scale improvements and consideration is given to the phased programme.
  • Chapter 572 of the statute of retention has been increased and the cost of delay is accumulated on a daily basis.

The point of departure for the line of responsibility and the lease is set out below.Substantive guidance on the scope of services: three lines of division of responsibilities。

XI. 2026 Annual legislation

  • Revision of the Safety and Security RegulationsThe Governance Report 2026 proposes a revision to strengthen the regulation of fire service installations and their contractors, introduce a system of manslaughter of fire service installations, increase penalties and strengthen Fire Services Department law enforcement powers, and submit recommendations to the Legislative Council in the course of the year.
  • Material networking fire detection system(a) Fire Services Department 2026 April 30 April 2001, 3/2026, which accommodates six layers or the target building under Chapter 572 below, using the system ' s appliance fire extinguisher as a substitute for witches and hand-held alarms; It is also planned to expand to seven or more old buildings before the end of 2026, and to include a fire safety improvement engineering support plan.
  • FS251 Full electronicization: Implemented from 1 July 2026 and expand the annual inspection checklist by approximately three times larger, covering about five active contractors.
  • Maintenance and supervision of buildings:: Reform of the old building maintenance system during the same period, including research on the criminalization of the building ' s main maintenance perimeter, the first solicitation and tendering services for hiring consultants and contractors for owners, and the expansion of the revised Buildings Regulations to tighten disciplinary regimes for professionals and contractors.

Continuous update of time framesfire safety information: Hong Kong fire safety statute time。

XII. PRACTICES

Does the penalty of Chapter 572 actually increase?

Yes. The penalty not subject to fire safety direction has been fined at level 4 (US$ 25,000) and US$ 2,500 per day, increasing to level 6 (US$ 100,000) and US$ 10,000 per day; Failure to comply with fire safety orders is a fine of 200,000 yuan and $20,000 per day. See tableCurrent penalties。

Does Chapter 502 address only the old building?

Not. (b) The construction of commercial premises is determined by the type of business activity and over 230 square metres of the total floor, not on the basis of the year in which they were landed; It is indicated that the commercial building blocks relate to old commercial buildings.

How does it know whether its building is the target building?

Fire Services Department (2272,9112) or ISA (262626,1616) can be checked and the notifications received may be forwarded to us for verification of scope and requirements.

What are the consequences of an annual inspection?

Failure to maintain an effective operational condition or the possibility of prosecution without a periodic check; When electronicized records are uploaded in time, and the size of the spot checks is expanded to make it easier for late and unavailable information to be identified.

Who will issue FS251?

A registered fire service installation contractor that has completed its work is issued to the person entrusted and a copy must be sent to Fire Services Department within 14 days.

Can non-registered contractors be used for minor maintenance?

It is not possible. Under Chapter 95B, a non-registered contractor shall not be permitted to install, maintain, repair or inspect fire service installations or equipment at any place.

What is generally involved in industrial building improvement?

The core is the addition of automatic sprinkler system and associated water sources, dams and kitchens, including alarm systems, emergency lighting, export instructions, copper, fire door and improved access to fire.

Is it only a warning to go through the flames?

Fire Services Department may issue notices to eliminate fire hazards; If the fire is repeated within 12 months of the notification, it can be prosecuted with a fine of 25,000 yuan and an additional amount of 2,500 dollars per day for a continuous period.

Can the old building replace traditional devices with new technologies?

Partially. (b) The six-tier or the following Chapter 572 target building has been replaced by a fire extinguisher fingerprint of the StAR system and is planned to be extended to the old floor of seven or more; The application must be confirmed on the basis of individual building and Fire Services Department requirements.

What should be done before instructions are received?