BS 476 Part 7 Class 1 vs Class 2: Understanding Surface Spread of Flame Standards and Test Reports for Hong Kong Fitting-Out Materials
The same sentence appears again and again in the Fire Services Department's (FSD) licensing requirements: "All combustible materials used for false ceilings, partitions or wall finishes shall conform to Class 1 or Class 2 of British Standard 476: Part 7 for surface spread of flame." Many fitting-out contractors and tenants know they need "Class 1 or Class 2", but are unsure what the two classes actually mean, how the test is carried out, or whether the reports from suppliers are valid. This article explains the standard from a technical angle and sets out how licensed premises in Hong Kong should check their documents in practice.
Quick answer: BS 476 Part 7 is a British test standard that measures the lateral spread of flame across the surface of a material, with results classified from Class 1 to Class 4. Class 1 has the shortest flame spread, while Class 2 allows slightly further spread. Both meet the FSD's general requirements for false ceilings, partitions and wall finishes in licensed premises, while Class 3 and Class 4 do not. Materials that fall short must be treated with a fire retardant paint or solution accepted by the Director of Fire Services by a Class 2 Registered Fire Service Installation Contractor, who then submits an FS251.
Contents
- The BS 476 series and where Part 7 fits
- How the Part 7 test works
- Classification limits for Class 1 to Class 4
- Practical differences between Class 1 and Class 2
- Class 0, EN 13501-1 and BS 5867-2
- FSD requirements in Hong Kong
- How to check a test report
- Common premises scenarios
- Frequently asked questions
1. The BS 476 Series and Where Part 7 Fits
BS 476 is a series of fire test standards for building materials and elements of construction published by the British Standards Institution. It covers several areas. The parts most often seen in fitting-out work are:
| Part | What it tests | Common use |
|---|---|---|
| Part 4 | Whether a material is non-combustible | Determining whether a material burns at all |
| Part 6 | Fire propagation index, measuring how much a material contributes to fire growth | Combined with Part 7 to determine the UK Class 0 |
| Part 7 | Lateral surface spread of flame | Wall and ceiling finishes, false ceilings, partitions |
| Parts 20 to 24 | Fire resistance of elements of construction | Fire doors, fire walls, structural elements |
As this shows, Part 7 is not about how many minutes a material can withstand fire. It is about how quickly and how far flame travels across its surface. False ceilings and wall finishes cover large areas at height, so if flame spreads rapidly across them, fire can engulf an entire space within a short time. That is why the FSD places such weight on this standard. For the basics of how fire retardant paint works, see What Is Fire Retardant Paint? Principles, Types and Hong Kong Fire Safety Requirements.
2. How the Part 7 Test Works
Understanding the test method helps you judge whether a report makes sense, and explains why the same material can achieve different classes under different conditions.
Test Apparatus
- Radiant panel: a gas-fired radiant panel heats the specimen, with an irradiance of 32.5 kW/m² at 75 mm from the specimen's starting edge. Irradiance decreases further along the specimen.
- Pilot flame: a small gas burner ignites the specimen at its starting edge, with a flame height of about 75 to 100 mm.
- Specimen: usually a rectangle of 885 mm × 270 mm, mounted vertically. Only specimens expected to achieve Class 1 may be shortened, to no less than 250 mm in length.
Test Procedure
- Timing starts as soon as the specimen is placed in the test position.
- The specimen is exposed to radiant heat for up to 10 minutes. The test ends early if the flame front reaches the 825 mm reference line.
- The time at which the flame front passes each reference line is recorded.
- The maximum flame spread within the first 1.5 minutes and over the whole test are recorded separately.
- The class is determined from six valid specimens, at least five of which must meet the limits for that class.
Because irradiance drops away from the starting edge, how far the flame travels shows whether the material can sustain and spread burning as the heat weakens. The shorter the flame spread, the less the surface contributes to fire growth.
3. Classification Limits for Class 1 to Class 4
Part 7 classifies materials by flame spread at two points in time:
| Class | Spread limit at 1.5 minutes | Final spread limit at 10 minutes | Single specimen allowance (1.5 min / final) |
|---|---|---|---|
| Class 1 | 165 mm | 165 mm | 190 mm / 190 mm |
| Class 2 | 215 mm | 455 mm | 240 mm / 500 mm |
| Class 3 | 265 mm | 710 mm | 290 mm / 785 mm |
| Class 4 | Exceeds Class 3 limits; high fire hazard and unsuitable as a building material | ||
The meaning behind the numbers is straightforward. With a Class 1 material, the flame stays close to the starting edge for the full 10 minutes, and the final spread is the same as at 1.5 minutes. A Class 2 material performs similarly at first, but the flame can then continue to about 455 mm. By Class 3, the final spread covers most of the specimen's length.
4. Practical Differences Between Class 1 and Class 2
Under the requirements for most licensed premises in Hong Kong, both Class 1 and Class 2 are acceptable. In practice, however, there are differences worth noting when choosing materials:
| Aspect | Class 1 | Class 2 |
|---|---|---|
| Flame behaviour | Flame essentially does not spread | Controlled at first, with some spread later |
| General licensed premises in Hong Kong | Compliant | Compliant |
| Typical materials | Gypsum board, mineral fibre ceiling tiles, some fire-rated boards and treated materials | Some fire-retardant-treated timber products and finishes |
| Suitable locations | Safer choice for escape routes, corridors, staircases and crowded areas | General indoor areas (subject to individual requirements) |
| Safety margin | Larger, easier to cope with future alterations or stricter rules | Smaller, may need reassessment if requirements change |
In practice, if the price difference is small, choosing Class 1 reduces the chance of being questioned later. The final decision should still follow the FSD's written requirements for that type of premises. Some premises or locations may have stricter requirements, so there is no one-size-fits-all answer.
5. Class 0, EN 13501-1 and BS 5867-2
Quotations and product data sheets often mention several standards at once. These three cause the most confusion.
Class 0 Is Not a BS 476 Part 7 Class
Class 0 is a combined classification used under UK building regulations. It generally requires a material to achieve Part 7 Class 1 and a Part 6 fire propagation index (I) of no more than 12. In other words, Class 0 is stricter than Part 7 Class 1. Requirements for general licensed premises in Hong Kong refer to Part 7 Class 1 or Class 2. Materials labelled Class 0 usually also have a Part 7 Class 1 result, but you should still check the Part 7 result stated in the report.
EN 13501-1 Cannot Be Converted Directly
The European standard EN 13501-1 uses classes A1, A2, B, C, D, E and F, with additional classifications for smoke (s1 to s3) and flaming droplets (d0 to d2). It uses different test methods and assessment criteria from BS 476, so the two cannot be converted directly. For example, "Class B" cannot be treated as equivalent to "Class 1". If a material only has an EN report, first confirm with the FSD or a registered contractor whether it is an equivalent standard accepted by the Director of Fire Services.
BS 5867-2 Applies to Drapes and Curtains
Hanging fabrics such as drapes and curtains are not assessed under BS 476 Part 7. FSD requirements generally state that drapes and curtains must be made of fire-resisting materials meeting the Type B performance requirements of BS 5867 Part 2 when tested to BS EN ISO 15025:2002. Otherwise they must be treated with a fire retardant solution accepted by the Director of Fire Services, with an FS251 submitted by a Class 2 registered contractor. Some premises also require drapes hung at exits to be split in the centre and kept at least 75 mm above the floor.
| Material | Applicable standard | Treatment if non-compliant |
|---|---|---|
| False ceilings, partitions, wall finishes | BS 476 Part 7 Class 1 or Class 2 | Treatment with an accepted fire retardant paint or solution |
| Drapes, curtains | BS 5867 Part 2 Type B | Treatment with an accepted fire retardant solution |
6. FSD Requirements in Hong Kong
In its letter to licensed and registered premises, the FSD states that linings used for acoustic, thermal or decorative purposes, wherever they form false ceilings, partitions or wall finishes, must meet BS 476 Part 7 Class 1 or Class 2, or an equivalent international standard, for flammability. Otherwise they must be treated by a Class 2 Registered Fire Service Installation Contractor with a fire retardant paint or solution accepted by the Director of Fire Services to achieve that standard, and an FS251 must be submitted after completion.
During Licence Applications and While Licensed
- When applying for a licence or registration: applicants must submit test reports for combustible materials for FSD verification. If materials are treated with fire retardant paint or solution, an FS251 must be submitted instead. Failure to comply may lead to the application being refused.
- When altering fitting-out while licensed: licensees must confirm the flammability standard of materials with their suppliers and submit test reports or an FS251, whichever applies. Failure to comply may be treated as a breach of licensing conditions, and the licensing authority may suspend or cancel the licence.
In other words, this requirement does not stop once the premises opens. Any later renovation, added partition or replaced ceiling must be checked against the material standard again. For an overview of Hong Kong fire safety legislation, see Hong Kong Fire Safety Laws and Regulations.
FSD Lists of Accepted Fire Retardant Solutions
The FSD publishes two separate lists: accepted fire retardant solutions for BS 476 Part 7, and accepted fire retardant solutions for BS 5867-2 Type B performance. The former applies to false ceiling, partition and wall materials; the latter applies to fabrics. When selecting a product, a contractor should confirm that it appears on the relevant list and apply it at the coverage and by the method specified for that product.
7. How to Check a Test Report
A supplier simply saying "it's Class 1" is not enough. At inspection, the FSD checks whether the documents match the materials on site. When you receive a test report, check it item by item against this list:
- Standard name: the report must clearly state BS 476: Part 7, not just "fireproof" or another standard.
- Test result: it must state Class 1 or Class 2, with flame spread data for each specimen.
- Product model: the product name, model, thickness and colour in the report must match the material actually purchased.
- Tested system: if the material is fixed with adhesive or installed on a particular substrate, the report should cover that whole system, not just the surface layer. For example, a report for ceiling film should cover the adhesive actually used.
- Test laboratory: check the laboratory name and report number so that the report can be traced.
- Validity: confirm that the product formulation and specification have not changed since testing.
- Matching purchase records: keep delivery notes or invoices to show that the material on site is the product described in the report.
A Common Scenario
A restaurant uses wood-grain decorative panels on its walls. The supplier provides a Class 1 report for the panels alone, but on site the panels are glued onto plywood with a different adhesive. Because the installed system differs from the tested system, the report may not be accepted as proof. The safer approach is to ask the supplier, before purchase, for a report that matches the actual installation method. If none is available, switch to another material, or have a Class 2 contractor apply fire retardant treatment before installation.
8. Common Premises Scenarios
New Restaurants
Restaurants are the premises most likely to face this requirement. At the design stage, list the material specifications for all false ceilings, timber partitions, wall finishes and curtains, and collect test reports at the same time. Materials without sufficient reports are best treated before painting, to avoid having to strip and redo work after completion.
Tutorial Schools, Places of Amusement and Clubs
These premises are subject to similar fire safety requirements to restaurants, but individual items vary with floor area, storey and use. Always follow the requirements the FSD issues for the specific premises.
Licensed Premises Under Renovation
Material changes made while a licence is in force are often overlooked. Even replacing one wall finish or adding one timber partition, you should confirm the standard of the new material and keep the report or FS251 ready for FSD inspection.
Exhibition Booths and Temporary Installations
Booths often use plywood and fabric backdrops, and build-up schedules are tight. Organisers or venues usually specify fire safety requirements, so exhibitors should confirm these early and allow time for fire retardant treatment and certification.
If your premises also needs other fire service installations, see our Fire Engineering Services. Premises already in operation should also keep up with annual fire service installation inspections; see our Complete Guide to Fire System Maintenance and FS251 Annual Inspection.
Pre-Selection Checklist
| Stage | What to do |
|---|---|
| Design | List materials, locations and areas for false ceilings, partitions, walls and fabrics |
| Procurement | Ask suppliers for BS 476 Part 7 or BS 5867-2 reports that match the installation method |
| Before installation | Arrange for a Class 2 registered contractor to treat materials lacking adequate reports before painting or assembly |
| After completion | Compile test reports, FS251, delivery notes and product information |
| While licensed | Recheck standards and keep documents for any material changes |
Frequently Asked Questions
Which is better, BS 476 Part 7 Class 1 or Class 2?
Class 1 has shorter surface flame spread and therefore better fire performance. For false ceilings, partitions and wall finishes in general licensed premises in Hong Kong, either Class 1 or Class 2 is acceptable, but some premises or locations may have stricter requirements. Always follow the FSD's written requirements.
Is Class 0 the same as BS 476 Part 7 Class 1?
Not exactly. Class 0 generally requires a material to meet both Part 7 Class 1 and the Part 6 fire propagation index requirement, making it stricter than Class 1 alone. When checking against Hong Kong requirements, look at the Part 7 result stated in the report.
Is an EN 13501-1 report acceptable on its own?
EN 13501-1 uses different test methods from BS 476, so its classes cannot be converted directly. If a material only has an EN report, first confirm with the FSD or a registered contractor whether it is an equivalent standard accepted by the Director of Fire Services.
Do curtains also need to meet BS 476 Part 7?
Curtains and drapes are generally subject to BS 5867 Part 2 Type B, not BS 476 Part 7. Non-compliant fabrics must be treated with a fire retardant solution accepted by the Director of Fire Services, with an FS251 submitted by a Class 2 registered contractor.
If a material has a Class 1 report, does it still need fire retardant paint?
If the report is valid and the product model and installation method match what is on site, no further treatment is generally needed and the test report serves as proof. If the report does not match the material on site, separate treatment is required.
What class does a material achieve after fire retardant treatment?
Fire retardant paints and solutions accepted by the Director of Fire Services are intended to bring materials up to Class 1 or Class 2 when applied according to the product requirements. The actual result depends on the product, the material and the workmanship, which is why the work must be done by a Class 2 registered contractor who issues an FS251.
Do I need to notify the FSD if I replace a ceiling after obtaining my licence?
If a licensee uses combustible materials or makes alterations involving them, the licensee must confirm the flammability standard of the materials and submit a test report or FS251, whichever applies, to the FSD. Failure to comply may be treated as a breach of licensing conditions.
Need Help Checking Your Material Documents?
Grand United Eng., Co. is a Registered Fire Service Installation Contractor in Hong Kong. We can help review test reports for false ceilings, partitions, wall finishes and fabrics, assess whether materials need fire retardant treatment, and arrange the related works and certificates. When you contact us, please provide the premises use, a list of materials, any existing reports and any FSD letter of requirements. You can also browse our Fire Safety Products, Project Cases and FAQ.