How to Provide Portable Fire Equipment for Construction Sites, Kitchens and Warehouses: A Complete Guide to Fire Extinguisher, Fire Blanket and Sand Bucket Numbers, Locations and Legal Requirements
"How many fire extinguishers do we need?" involves completely different considerations on a construction site, in a restaurant kitchen and in a warehouse. On a construction site, the risks come from welding, fuel and debris, and the environment changes every day. In a kitchen, the risks are concentrated around burners, hot oil and gas, and a fire can grow within seconds. In a warehouse, large quantities of combustible goods are stored together, and once a fire starts it is very hard to control. Based on the Fire Services Department (FSD), the Labour Department and relevant legislation, this guide sets out the portable fire equipment requirements, provision advice, placement principles and common mistakes for each of the three settings.
Quick answer: Under FSD standards, restaurant kitchens generally need 4.5 kg CO2 fire extinguishers, 9-litre water or 5 kg dry powder fire extinguishers, and 1.44 m² fire blankets, with the number and location set out in the FSD's written requirements. Under Labour Department guidance, construction sites must provide and maintain fire extinguishers and sand buckets near the work area before hot work such as welding begins. For prescribed commercial premises such as warehouses, the Fire Safety (Commercial Premises) Ordinance requires at least one portable fire extinguisher for every 100 m² of floor area (except premises with a hose reel system), and clearance must be kept around sprinkler heads with fire-fighting equipment kept visible and easy to reach.
Contents
- Common principles for providing portable equipment
- Restaurant and commercial kitchens
- Construction sites
- Warehouses and godowns
- The three settings compared
- Examples of estimating numbers
- The most common mistakes in each setting
- Staff training and drills
- Frequently asked questions
1. Common Principles for Providing Portable Equipment
Whatever the setting, portable fire equipment can be provided according to the following principles:
| Principle | What to do |
|---|---|
| Check the requirements first | For licensed premises, prescribed commercial premises, dangerous goods premises and so on, provide equipment according to the legislation, licence conditions or the FSD's written requirements first |
| Choose the type by risk | Electrical equipment, flammable liquids, cooking oil and ordinary solids each need suitable appliances |
| Near the risk but not next to the fire source | Place equipment near the risk, but not where it would be cut off by the fire |
| On the escape side | The user fights the fire with their back to the exit, keeping an escape route open |
| Visible and easy to reach | Not hidden behind goods or clutter, with a clear path in front |
| Approval and maintenance | Fire extinguishers and fire blankets must be FSD-approved and checked as required |
For the differences between appliances, see Fire Buckets, Fire Extinguishers or Fire Blankets: How to Choose?. For how to check approved equipment, see How to Tell Whether Portable Fire-Fighting Equipment Is FSD-Approved.
2. Restaurant and Commercial Kitchens
Risk Analysis
- Hot oil and deep frying: overheated oil can catch fire, and the fire can grow within seconds.
- Kitchen exhaust systems: grease builds up in cooker hoods and ducts, allowing fire to spread along the ductwork.
- Town gas and LPG: leaks can cause fire or explosion.
- Electrical equipment: refrigerators, ovens, electric griddles and similar run for long hours.
FSD Portable Equipment Requirements
The FSD's fire safety standards for general (fast food) restaurants state that, in addition to the fire service installations in the building, approved portable fire-fighting equipment must be provided at the locations and in the numbers specified by the FSD for the individual premises:
| Appliance | Specification | Common location | Main use |
|---|---|---|---|
| CO2 fire extinguisher | 4.5 kg | Near the kitchen burners | Electrical and flammable liquid fires |
| Water or dry powder fire extinguisher | 9-litre water or 5 kg dry powder | Near exits | Ordinary solid fires in the seating area |
| Fire blanket | 1.44 m² | Kitchen | Wok or pan fires and other small fires |
The actual numbers and locations are set out in the written requirements the FSD issues to individual applicants. For overall restaurant fire safety requirements, see Fire Retardant Paint and False Ceiling Requirements for Restaurants.
Automatic Fire Suppression Systems
Portable equipment is only the first line of defence. The FSD's fast food restaurant standards also state that, at all stoves, cooking ranges and deep frying locations, in addition to an automatic sprinkler system, an automatic fire control or suppression system must be installed. The system must comply with UL-300 "Fire Testing of Fire Extinguishing Systems for Protection of Commercial Cooking Equipment", or another equivalent standard accepted by the Director of Fire Services. Portable equipment should work alongside these systems, not replace them.
Kitchen Placement Principles
- Place CO2 extinguishers near the burners, but not directly above or right next to them, where they could be heated or cut off by the fire.
- Hang the fire blanket on the wall near the kitchen entrance, within easy reach.
- Do not place appliances where grease or steam collects, as labels may become illegible or parts damaged.
- Place water or dry powder extinguishers for the seating area near the exits.
Sand Buckets Are Not Recommended in Kitchens
Pouring sand onto a wok or pan fire may cause hot oil to splatter, so kitchens should rely mainly on fire blankets and suitable fire extinguishers. Only if the kitchen also stores fuel or solvents does this need separate assessment.
3. Construction Sites
Risk Analysis
- Hot work: electric arc welding, flame cutting and grinding produce sparks and high temperatures.
- Flammable materials: fuel, paints, solvents, foam and protective materials on external scaffolding.
- Debris and waste: timber, packaging materials and rubbish.
- Temporary power: temporary wiring and equipment.
- Changing conditions: work progresses every day, so equipment locations must be adjusted accordingly.
Legislation and Guidance
Section 54 of the Construction Sites (Safety) Regulations (Cap. 59I) requires the contractor responsible for a construction site to keep all means of escape and fire-fighting appliances provided on the site in good condition and free from obstruction.
The Labour Department's systematic safety alert on fire safety on construction sites requires contractors to:
- Appoint a competent person to carry out task-specific risk assessments to identify fire and explosion hazards arising from the use of flammable materials, protective materials on external scaffolding, hot work and electrical installations or equipment
- Implement a total smoking ban on construction sites
- Replace flammable materials with non-flammable ones as far as possible
- Prohibit hot work near flammable or combustible materials
- Before hot work, keep the work area tidy and remove flammable materials or cover them with fire-resistant materials
- Provide and properly maintain fire-fighting equipment near the work area, such as fire extinguishers and sand buckets
- Provide and properly maintain adequate fire service installations and equipment, such as fire detection equipment, fire alarm systems, fire pumps and fire extinguishers
The FSD also issues fire safety measures for construction sites, which set out the ratio of 9-litre water portable fire extinguishers to floor area and the minimum number per floor. Contractors should follow the latest version and the works contract requirements.
Construction Site Provision Advice
| Location | Suggested appliances |
|---|---|
| Welding and cutting work areas | Fire extinguishers and sand buckets, moved with the work |
| Fuel storage and refuelling locations | Sand buckets, dry powder or foam extinguishers |
| Each working floor | 9-litre water extinguishers, in the ratio set by FSD guidance |
| Temporary switch rooms, generators | CO2 or dry powder extinguishers |
| Paint and solvent storage | Sand buckets, dry powder or foam extinguishers |
| Site offices | Water and CO2 extinguishers, or dry powder extinguishers |
Construction Site Placement Principles
- Fire extinguishers and sand buckets for hot work should be in place before work starts and only removed once it is finished.
- Sand buckets and extinguishers in outdoor locations should be covered to protect them from rain and sun.
- Inspect daily to make sure appliances are not blocked by materials, scaffolding or waste.
- Update the equipment location plan as work progresses.
- Mark appliance locations clearly so workers can find them even on unfamiliar floors.
4. Warehouses and Godowns
Risk Analysis
- Concentrated combustibles: large quantities of cardboard boxes, plastics, fabrics and packaging materials stored together.
- Stacking too high: obstructs sprinklers and lets fire spread vertically.
- Blocked aisles: goods occupy aisles and hide fire-fighting equipment.
- Forklifts and charging: charging areas for electric forklifts carry an electrical fire risk.
- Dangerous goods: some warehouses store flammable liquids or chemicals.
Legal Requirements
Schedule 3 to the Fire Safety (Commercial Premises) Ordinance (Cap. 502) requires prescribed commercial premises to have at least one portable fire extinguisher for every 100 m² of floor area (any part of 100 m² being counted as 100 m²). This does not apply to premises with a hose reel system installed. Whether a warehouse is a prescribed commercial premises depends on its use and floor area; if it is, this ratio must be followed.
If a warehouse stores dangerous goods above the exempt quantity, it must obtain an FSD licence and provide fire-fighting appliances according to the licence conditions; see Which Premises in Hong Kong Need Fire Buckets or Sand Buckets?.
Sprinkler Head Clearance
The FSD states that a space of 0.5 m below sprinkler heads should generally be kept free of any obstruction, and the Occupational Safety and Health Council also recommends keeping at least 500 mm around sprinklers clear of obstructions. Goods stacked too high will stop sprinklers from discharging water effectively.
Warehouse Provision Advice
| Location | Suggested appliances |
|---|---|
| Rack aisles | Water or dry powder extinguishers, distributed by floor area |
| Entrances and exits | Fire extinguishers |
| Forklift charging areas, switch rooms | CO2 or dry powder extinguishers |
| Flammable liquid storage areas | Sand buckets, foam or dry powder extinguishers |
| Packing areas | Water or dry powder extinguishers |
Warehouse Placement Principles
- Place fire-fighting equipment in conspicuous locations, with enough space nearby for access.
- Mark no-stacking zones on the floor in front of fire-fighting equipment.
- Keep the workplace tidy and store goods systematically, reducing the chance of goods being stacked too high or in front of fire-fighting equipment.
- Inspect regularly and correct any obstruction immediately.
5. The Three Settings Compared
| Aspect | Restaurant kitchen | Construction site | Warehouse |
|---|---|---|---|
| Main risks | Hot oil, gas, electrical equipment | Hot work, fuel, debris | Concentrated combustible goods, stacking too high |
| Main appliances | CO2 extinguishers, fire blankets, water or dry powder | Fire extinguishers, sand buckets, water extinguishers | Water or dry powder extinguishers, distributed by floor area |
| Sand buckets | Generally not recommended | Common, especially for hot work and fuel locations | Suitable for flammable liquid areas |
| Main basis | FSD fire safety standards for restaurants | Cap. 59I, Labour Department guidance, FSD measures for construction sites | Schedule 3 to Cap. 502 (if applicable), dangerous goods licence |
| Changing conditions | Fairly fixed | Changes daily | Changes with stock levels |
| Most common problems | Equipment covered in grease, placed in the wrong location | Blocked by materials, not moved with the work | Blocked by goods, insufficient sprinkler clearance |
6. Examples of Estimating Numbers
These examples only illustrate how to think through the calculation. Actual numbers follow the applicable legislation and written requirements.
Example 1: A 350 m² Warehouse That Is a Prescribed Commercial Premises
Under Schedule 3 to Cap. 502, there must be at least one portable fire extinguisher for every 100 m², with any part of 100 m² counted as 100 m². 350 m² is therefore counted as 400 m², requiring at least 4 portable fire extinguishers. If the warehouse has a hose reel system installed, this ratio does not apply, but it is still advisable to provide suitable appliances for the forklift charging area and flammable liquid area.
Example 2: A Small Fast Food Outlet
The FSD's written requirements will set out the number and location of 4.5 kg CO2 extinguishers, 9-litre water or 5 kg dry powder extinguishers, and 1.44 m² fire blankets to be provided. A common arrangement is to place the CO2 extinguisher near the burners, the water or dry powder extinguisher near the exit, and the fire blanket in the kitchen.
Example 3: Welding on One Floor of a Construction Site
Under Labour Department guidance, before welding begins, fire extinguishers and sand buckets should be placed near the work area, and flammable materials nearby should be removed or covered. The number of water extinguishers on that floor follows the ratio in the FSD's fire safety measures for construction sites.
7. The Most Common Mistakes in Each Setting
Kitchens
- Fire extinguishers placed directly above the burners or in a corner, so they cannot be reached in a fire
- Fire blankets covered by clutter or kept in a cupboard
- Appliances covered in grease, with illegible labels
- Water used on wok or pan fires
- Staff not knowing where the fire blanket is or how to use it
Construction Sites
- No fire extinguishers or sand buckets nearby during welding
- Appliances blocked by scaffolding, materials or waste
- Sand buckets left out in the rain, with clumped sand
- Appliances not moved as the work progresses
- Appliances borrowed and not returned to their place
Warehouses
- Goods stacked in front of fire extinguishers
- Goods stacked within 500 mm below sprinkler heads
- The number of extinguishers not increased as the warehouse expands
- No appliances suitable for electrical fires in the forklift charging area
- Flammable liquids stored together with ordinary goods
8. Staff Training and Drills
However well equipment is provided, it is useless if staff do not know how to use it. We recommend:
- Showing new staff the location and use of appliances when they join
- Holding regular demonstrations of fire extinguishers and fire blankets
- Displaying appliance location plans and emergency procedures
- Stressing safety first: if the fire grows, evacuate immediately and call 999
- Reporting to the person in charge straight after any appliance is used, so it can be refilled or replaced
For annual inspection of portable equipment and FS251 arrangements, see our Complete Guide to Fire System Maintenance and FS251 Annual Inspection. For sand bucket maintenance, see How to Maintain a Sand Bucket and How Often to Change the Sand.
9. Frequently Asked Questions
What fire-fighting appliances does a restaurant kitchen need?
Under the FSD's fire safety standards for general (fast food) restaurants, the premises generally needs 4.5 kg CO2 fire extinguishers, 9-litre water or 5 kg dry powder fire extinguishers, and 1.44 m² fire blankets. The number and location follow the FSD's written requirements.
Besides portable equipment, what else does a kitchen need?
At the stoves, cooking ranges and deep frying locations of fast food restaurants, in addition to an automatic sprinkler system, an automatic fire control or suppression system complying with UL-300 or an equivalent standard accepted by the Director of Fire Services must be installed.
What fire-fighting equipment is needed for welding on a construction site?
Labour Department guidance requires fire-fighting equipment, such as fire extinguishers and sand buckets, to be provided and properly maintained near the work area before hot work begins, and flammable materials nearby to be removed or covered with fire-resistant materials.
How many fire extinguishers are needed on each floor of a construction site?
The FSD's fire safety measures for construction sites set out the ratio of 9-litre water portable fire extinguishers to floor area and the minimum number per floor. Contractors should follow the latest version and the works contract requirements.
How many square metres per fire extinguisher in a warehouse?
If the warehouse is a prescribed commercial premises under the Fire Safety (Commercial Premises) Ordinance, there must be at least one portable fire extinguisher for every 100 m² of floor area (any part of 100 m² counted as 100 m²), except where a hose reel system is installed.
How high can goods be stacked in a warehouse?
The FSD states that a space of 0.5 m below sprinkler heads should generally be kept free of obstruction, and the Occupational Safety and Health Council also recommends keeping at least 500 mm around sprinklers clear.
Can sand buckets be used in a kitchen?
It is not recommended. Pouring sand onto a wok or pan fire may cause hot oil to splatter, so kitchens should rely mainly on fire blankets and suitable fire extinguishers.
Can a construction site sand bucket be left outdoors?
It should be kept in a covered location with the lid on, to stop rain from making the sand damp and clumped. Outdoor locations should be checked more often.
What fire-fighting appliances should be provided in a forklift charging area?
Charging areas mainly carry an electrical fire risk, so CO2 or dry powder extinguishers are generally suitable. Keep combustible goods from being stacked near the charging area.
Can fire extinguishers be placed behind goods?
No. Fire-fighting equipment should be placed in conspicuous locations, with enough access space nearby so it can be reached quickly in an emergency. Marking no-stacking zones on the floor is recommended.
Portable Fire Equipment Provision and Inspection
Grand United Eng., Co. is a Registered Fire Service Installation Contractor in Hong Kong. We can assess fire risks for restaurant kitchens, construction sites, warehouses and all types of premises, advise on the type, number and location of fire extinguishers, fire blankets and sand buckets, supply FSD-approved portable equipment, and arrange annual inspections and the FS251. When you contact us, please provide the premises type, floor area, floor plan, main risks and any relevant requirements. You can also browse our Fire Safety Products, Fire Engineering Services and Service Coverage.
Enquire about portable fire equipment provision, or call 2667 7701.