What Are Fire Buckets and Sand Buckets? A Complete Guide to FSD Specifications, Uses, How to Use Them and Where to Place Them

Walk into a generator room, fuel tank room, construction site or petrol station and you will often see a red bucket with a lid, marked "SAND" or with the Chinese character for sand. This is what people in Hong Kong commonly call a "fire bucket", and its proper name is a fire sand bucket. It may look simple, but it is a piece of fire-fighting equipment whose specification is set out in the Fire Services Department's (FSD) codes of practice, with requirements covering capacity, colour, labelling, the condition of the sand and how full it must be. This guide explains sand bucket specifications, uses, how to use them, placement principles and inspection requirements, based on the FSD's code.

Quick answer: In Hong Kong, a fire bucket usually means a fire sand bucket: a portable hand-operated appliance holding dry sand, used to control and extinguish small fires involving flammable liquids. Under the FSD's Codes of Practice for Minimum Fire Service Installations and Equipment, a sand bucket must be made of durable material, have a lid, have a capacity of not less than 9 litres, be finished in red with suitable Chinese and English labels, contain dry sand only, and be filled to at least 80% of its capacity. Sand buckets should be inspected every 12 months or after use in a fire.

Contents

  1. Defining fire buckets and sand buckets
  2. The FSD's six sand bucket specifications
  3. Why sand buckets put out fires
  4. How to use a sand bucket correctly
  5. Limits and unsuitable situations
  6. Common locations for sand buckets
  7. Practical placement principles
  8. Inspection and maintenance requirements
  9. What to check when buying a sand bucket
  10. Frequently asked questions

1. Defining Fire Buckets and Sand Buckets

The term "fire bucket" means different things in different places. In some countries, a fire bucket can be a red bucket filled with water. In everyday usage and in the fire safety industry in Hong Kong, however, a "fire bucket" usually refers to a fire sand bucket holding dry sand. It is also known as a "fire-fighting sand bucket" or "fire protection sand bucket".

In the FSD's code, sand buckets, like fire extinguishers and fire blankets, are classed as "portable hand-operated appliances", meaning any fire service equipment used as a standalone appliance to extinguish, attack, prevent or limit a fire. This means a sand bucket is not just any bucket, but fire-fighting equipment with a defined specification.

NameCommon meaningNotes
Fire bucketIn Hong Kong, usually a fire sand bucketColloquial term
Sand bucket, fire sand bucketFire-fighting appliance holding dry sandTerm used in the code
Fire protection sand bucketAs aboveTerm commonly used in the industry
Water bucketA bucket holding waterNot the sand bucket referred to in the FSD code

2. The FSD's Six Sand Bucket Specifications

Under the heading "portable hand-operated approved appliances", the FSD's Codes of Practice for Minimum Fire Service Installations and Equipment state that sand buckets must meet the following six specifications:

SpecificationRequirementWhat it means in practice
(a) MaterialMade of durable materialUsually metal or durable plastic that can be stored long-term without easily deteriorating
(b) LidFitted with a lidKeeps debris, moisture and rubbish out of the bucket
(c) CapacityNot less than 9 litresCheck the capacity marking when buying
(d) Colour and labelsFinished in red, with suitable Chinese and English labels stating that the sand is for fire-fightingEasy to identify in an emergency and prevents misuse for other purposes
(e) ContentsDry sand onlyNo rubbish, cigarette ends, oil or other items mixed in
(f) Fill levelFilled to at least 80% of capacityTop up if the sand level is low

The code also states that other portable hand-operated appliances must be approved by the Director of Fire Services and comply with the Fire Service (Installations and Equipment) Regulations (Cap. 95B). In other words, appliances such as fire extinguishers and fire blankets must be approved, while sand buckets are judged against the specification above. How to identify approved portable equipment is explained in detail in another article in this series.

What the Label Should Say

The code requires the label to "state that the sand is for fire-fighting", in both Chinese and English. A common approach is to print the Chinese for "fire sand bucket" together with "FIRE SAND BUCKET" or "SAND FOR FIRE FIGHTING" on the bucket. Labels should be clear and durable, and replaced if they fade or come off.

3. Why Sand Buckets Put Out Fires

Combustion needs three things: fuel, heat and oxygen. A sand bucket works in two main ways:

The FSD's code also explains that sand buckets are suitable for extinguishing fires involving flammable liquids, by pouring the sand onto the spilled flammable liquid to stop it from flowing around. This is why sand buckets are mostly placed near fuel, solvents and chemicals.

Why Water Should Not Be Used on Oil Fires

Fuel oil is less dense than water and floats on it. If water is thrown onto an oil fire, the water sinks beneath the oil and the burning oil can spread with the water. At high temperatures, water also turns to steam rapidly, which may cause burning oil to splatter. For small fires involving flammable liquids, use a sand bucket or a suitable fire extinguisher, not a water bucket.

4. How to Use a Sand Bucket Correctly

  1. Make sure you are safe: first confirm that the fire is small and that you have a safe escape route, and that others have been alerted and the fire reported (if needed).
  2. Open the lid: remove the lid and lift the bucket.
  3. Pour from the outside in: stand upwind and pour the sand from the outer edge of the fire or liquid towards the centre, first containing the flow of liquid and then covering the source of the fire.
  4. Avoid scattering: pour close to the ground and avoid throwing the sand hard, which could scatter sand and burning material.
  5. Cover completely: make sure the fire and flammable liquid are fully covered with sand.
  6. Keep watching: do not rake the sand apart straight after the fire is out; watch for re-ignition.
  7. Inspect and refill after use: the sand bucket must be inspected after use and refilled with dry sand.

Important: sand buckets are only suitable for small fires at an early stage. If the fire grows, smoke becomes thick or the fire cannot be controlled, evacuate immediately and call 999. Never take risks trying to fight it.

5. Limits and Unsuitable Situations

SituationIs a sand bucket suitable?Notes
A small amount of spilled fuel or solvent on the floor catching fireSuitableThe main use of a sand bucket
Containing a fuel leak that has not caught fireSuitableAbsorbs and contains liquid, reducing the risk of fire
Large or spreading firesNot suitableEvacuate and call the fire services
Wok or pan firesNot recommendedPouring sand may cause hot oil to splatter; a fire blanket or suitable extinguisher is better
Live electrical equipment on fireNot recommended as a first choiceCut off the power first and use an extinguisher suitable for electrical fires
Fires at height or on vertical surfacesNot suitableSand cannot stay in place to cover the fire
Burning gas leaksNot suitableCut off the gas supply and evacuate

A sand bucket is a supplementary appliance and cannot replace fire extinguishers, fire blankets, hose reels or other fire service installations. How to choose between different fire-fighting appliances is compared in detail in the article "Fire Buckets, Fire Extinguishers and Fire Blankets: How to Choose" in this series.

6. Common Locations for Sand Buckets

Whether sand buckets are needed, and how many, depends on the requirements issued by the FSD or other departments for the individual premises. The following are places where sand buckets are commonly provided in practice:

LocationReason
Emergency generator roomsGenerators run on diesel, with a risk of fuel leaks
Fuel tank roomsFuel oil is stored there
Petrol stationsPetrol and diesel are handled constantly
Dangerous goods storesFlammable liquids or chemicals are stored there
Construction sitesFuel-powered machinery and solvents are used, and hot work is carried out
Garages and vehicle repair workshopsEngine oil, petrol and solvents are handled
Factories and workshopsFlammable solvents, paints or fuels are used
LaboratoriesFlammable chemicals are used
Vessels and piersFuel is supplied and stored

Hong Kong legislation also contains express requirements for dry sand. For example, the Factories and Industrial Undertakings (Work in Compressed Air) Regulations (Cap. 59M) require the relevant facilities to be provided with 2 buckets of dry sand. Requirements for different premises are set out in the article "Which Premises in Hong Kong Need Fire Buckets or Sand Buckets?" in this series.

7. Practical Placement Principles

The FSD code sets out the specification for sand buckets, but the placement and number for individual premises are generally determined by the written requirements of the FSD or licensing authority. Where nothing specific is stated, the following practical principles can be used as a guide:

Location

Environment

Management

Common Mistakes

MistakeProblem
Sand bucket without a lidDoes not meet the specification; debris and moisture get in easily
Cigarette ends and rubbish in the bucketBreaches the "dry sand only" requirement and could even start a fire
Sand less than half fullBreaches the requirement to be at least 80% full
Sand has clumpedHard to pour out in an emergency
Placed behind clutterHard to reach in an emergency
Faded or missing labelDoes not meet the specification and is hard to identify

8. Inspection and Maintenance Requirements

The FSD code states that sand buckets should be inspected every 12 months or after use in a fire. Maintenance is as follows:

Metal Sand Buckets

  1. Inspect the condition of the metal bucket and lid
  2. Where necessary, repaint in red and re-apply the Chinese and English labels
  3. Replace badly corroded parts
  4. Check the amount of sand in the bucket and refill where necessary
  5. Dry out any damp sand

Plastic Sand Buckets

Likewise, inspect the condition of the bucket and lid, and check the amount of sand, whether it is dry, and whether the label is clear. Replace plastic buckets that are cracked, aged or deformed.

Detailed maintenance methods and when to replace the sand are explained in the article "How to Maintain Sand Buckets and How Often to Change the Sand" in this series. For annual inspection of portable equipment and FS251 arrangements, see our Complete Guide to Fire System Maintenance and FS251 Annual Inspection.

9. What to Check When Buying a Sand Bucket

Item to checkConfirmed
Made of durable material (metal or durable plastic)□
Fitted with a lid□
Capacity of not less than 9 litres□
Finished in red□
Chinese and English labels stating the sand is for fire-fighting□
Already filled with dry sand, or dry sand bought separately, filled to at least 80%□
Fitted with a handle for easy lifting□

Metal vs Plastic Buckets

AspectMetal sand bucketPlastic sand bucket
Heat resistanceBetterMay deform at high temperatures
RustMay rust in damp conditions; check regularlyDoes not rust
WeightHeavierLighter
Suitable environmentHotter locations such as generator rooms and workshopsDamper locations or covered outdoor areas

Use dry, clean sand free of debris. Do not use sand taken casually from construction sites or beaches, which may contain moisture, salt or impurities.

10. Frequently Asked Questions

Are a fire bucket and a sand bucket the same thing?

In Hong Kong, a fire bucket generally means a fire sand bucket: a red bucket with a lid that holds dry sand for fire-fighting. The term used in the FSD's code is "sand bucket".

What is the minimum size of a sand bucket?

Under the FSD's Codes of Practice for Minimum Fire Service Installations and Equipment, a sand bucket must have a capacity of not less than 9 litres and be filled to at least 80% of its capacity.

Does a sand bucket have to be red?

Yes. The code requires sand buckets to be finished in red, with suitable Chinese and English labels stating that the sand is for fire-fighting.

Does a sand bucket have to have a lid?

Yes. The code requires sand buckets to be fitted with a lid to keep out debris and moisture, so the sand stays dry and clean.

What fires can a sand bucket be used on?

The FSD's code states that sand buckets are suitable for extinguishing fires involving flammable liquids, by pouring the sand onto the spilled liquid to stop it from flowing around. Sand buckets are only suitable for small fires at an early stage.

Can sand be poured onto a wok or pan fire?

It is not recommended, as pouring sand into a pan may cause hot oil to splatter. For a pan fire, turn off the heat and use a fire blanket or a suitable fire extinguisher to cover or extinguish it.

Can a water bucket be used instead of a sand bucket?

No. Water is unsuitable for flammable liquid fires, because fuel oil floats on water and spreads with it. The FSD's code refers to sand buckets holding dry sand.

How often must a sand bucket be inspected?

Under the FSD's code, sand buckets should be inspected every 12 months or after use in a fire, including checks on the bucket, lid, label, amount of sand and whether the sand is dry.

What should I do if the sand in the bucket gets wet?

The code requires damp sand to be dried out. If the sand has clumped or contains impurities, replace it with clean dry sand and find the cause of the damp, such as a leak or a lid left off.

Where should a sand bucket be placed?

Generally near where flammable liquids are used or stored, in a place where it is easy to see and reach, preferably near an entrance or exit, and without obstructing walkways or other fire service installations. The exact location and number follow the written requirements of the FSD or licensing authority.

Can a sand bucket be used as an ashtray?

No. The code requires sand buckets to contain dry sand only. Mixing in cigarette ends and rubbish breaches the specification and could even start a fire.

Sand Bucket and Portable Fire Equipment Enquiries

Grand United Eng., Co. is a Registered Fire Service Installation Contractor in Hong Kong. We can assess the provision of portable fire-fighting equipment for generator rooms, fuel tank rooms, workshops, construction sites and all types of premises, supply sand buckets that meet the specification, and arrange inspections and the FS251. When you contact us, please provide the premises type, address, site photos and any FSD letter of requirements. You can also browse our Fire Safety Products, Fire Engineering Services and Service Coverage.

Enquire about sand buckets and portable fire equipment, or call 2667 7701.